Basic programming
Parameter
Default
0
Name
Value
SHIFT 1
On / Raise
On
Off / Lower
Off
Walk test
Off
On
Time Out
20 mins
1, 10 &
(Time
20
adjustment)
minutes
Lux on
9
2, 5 & 7
level
(Switch
level on)
Light Level
6 (600)
Lux off
9
2, 5 & 7
level
(Switch
level off)
Load Type
DALI
Sensitivity
9
1, 5 & 9
Defaults
Burn-in
0
0
Presence /
Presence Presence
Absence
Shift
8
The functionality of the MWS3A-DD-LV is controlled by a number of parameters which can
be changed or programmed by any of the following devices:
UHS5 Infrared Handset. See below for programmable functions.
UNLCDHS Infrared Handset (with LCD). See user guide for full programming details.
For most basic programming operations the UHS5 handset can be used and the following procedures
are based on using this device.
Point the handset at the Sensor and send the required programming commands to the unit as shown
below.
Valid commands will be indicated by a red LED flash. See page 1 for details of other LED responses.
Note: other functions on the UHS5 which are not shown below are not applicable to this product.
Number of Shift key presses
1
2
3
SHIFT 2
SHIFT 1
SHIFT 2
SHIFT 1
SHIFT 2
SHIFT 1
Button Activation
Raise
Lower
Off
5, 15 &
10
30
seconds
minutes
4, 6 & 9
2 (200)
4 (400)
5 (500)
6 (600)
7 (700)
9 (999)
4, 6 & 9
2-DALI
2-DALI
7-DSI
on
3, 6 & 8
D
50
100
Absence
UHS5 Handset Graphics
SHIFT 2
Description
Turn lights on or to raise lights.
Turn lights off or to lower lights.
When set to On this causes a red LED to flash on
the sensor when it detects movement. Use this
feature to check for adequate sensitivity levels.
Once the detector is turned on, this value sets
how long the lights will stay on once movement
has ceased.
Lux level setting to prevent the luminaires being
switched on if the ambient light level is sufficient
(adjustable between 1 and 9). The luminaires will
always be switched on at level 9.
Sets a target light level to be maintained by the
lighting system.
9 (999) = disabled.
Lux level setting to switch the luminaires off during
occupancy if the ambient light level goes above
the setting (adjustable between 1 and 9). Level 9
will always keep the lights on. This setting can be
used for "window row switching".
Note: the Lux Off Level value must always be
greater than the Lux On Level value.
Sets the ballast control protocol to be used by the
output channel.
Sensitivity level for detecting movement.
1 = low sensitivity
9 = high sensitivity
Returns the unit to the default settings.
Determines how long the output will be at 100%
so that lamps 'burn-in'. The 'burn-in' time is not
affected by power supply interruptions.
Presence mode allows the output to turn on when
movement is detected and off when movement
ceases. Absence mode allows the output to turn
off when movement ceases, but must be manually
turned on first.
Use this button to select the settings in red and
blue signified by the 'Shift 1' and 'Shift 2' LEDs