MAINTENANCE
1. Check Vacuum Pump Oil level before using the unit. If level is low, add. If oil turns
yellowish-brown, change oil.
2. Check service hose gaskets and o-rings for wear. Replace if necessary.
3. Check o-ring seal in Couplers for wear. Replace if necessary.
4. Check to make sure the oil drain system is function. Open drain valve and check for
failure to perform the oil drain function after each recovery, could lead to excessive
oil in the compressor and eventual compressor slugging.
1 - Exhaust / Refill Cap 2 - Oil Sightglass 3 - Oil Drain
Interconnection Hoses, Service Hoses and Coupler Maintenance
The AR2700 series uses brass to brass seal type fitting on the ends of the internal
interconnecting hoses. No hose gasket maintenance is required on the brass to brass
type of connections. Periodically inspect the refrigerant hose assembly, both service
hose ends and both service couplers (if used) inner O-ring. Replace the component(s)
if excessive wear or leakage is observed. Periodically leak-check all hose connection
points, hose ball valves, and service couplers (if used). Since this unit does pull a
vacuum in the recovery process, excessive Non-Condensable Gases (NCG's) could be
sucked into the system and placed in the storage tank.
Additonal Maintenance
1
2
3