Dell P570 Instrukcja obsługi - Strona 25

Przeglądaj online lub pobierz pdf Instrukcja obsługi dla Serwer Dell P570. Dell P570 35 stron.
Również dla Dell P570: Instrukcja obsługi (37 strony), Instrukcja obsługi (35 strony)

Dell P570 Instrukcja obsługi
Expanded operating temperature
Continuous operation
≤ 1% of annual operating hours
NOTE:
When operating in the expanded temperature range, VxRail performance may be impacted.
NOTE:
When operating in the expanded temperature range, ambient temperature warnings may be reported in the System
Event Log.
Expanded operating temperature restrictions
● Do not perform a cold startup below 5°C.
● The operating temperature specified is for a maximum altitude of 3050 m (10,000 ft).
● 150 W/8 core, 165 W/12 core and higher wattage processor [Thermal Design Power (TDP)>165 W] are not supported.
● Redundant power supply units are required.
● Non-Dell qualified peripheral cards and/or peripheral cards greater than 25 W are not supported.
● Mid drive tray is not supported.
● Rear storage devices or drives are not supported.
Thermal restrictions
This section describes the thermal restrictions and configuration requirements for efficient cooling.
The following table describes the configuration required for efficient cooling:
Supported
Number
VxRail
of
Configuratio
processo
n
r
VxRail P
1
Series
VxRail P
2
Series
VxRail S
1
Series
VxRail S
2
Series
Heatsink
One 1U standard heat sink
for CPU ≤ 125 W
One 2U standard heat sink
for CPU > 125 W
Two 1U standard heat sink
for CPU ≤ 125 W
Two 2U standard heat sink
for CPU > 125 W
One 1U high performance
heat sink
Two 1U high performance
heat sink
Specifications
5°C to 40°C at 5% to 85% RH with 29°C dew point.
NOTE:
Outside the standard operating temperature (10°C to
35°C), the VxRail can operate continuously in temperatures as low
as 5°C and as high as 40°C.
For temperatures between 35°C to 40°C, de-rate maximum allowable
temperature by 1°C per 175 m above 950 m (1°F per 319 ft).
–5°C to 45°C at 5% to 90% RH with 29°C dew point.
NOTE:
Outside the standard operating temperature (10°C to
35°C), the VxRail can operate down to –5°C or up to 45°C for
a maximum of 1% of its annual operating hours.
For temperatures between 40°C and 45°C, de-rate maximum
allowable temperature by 1°C per 125 m above 950 m (1°F per 228
ft).
Processor/DIMM
blank
Required
Not required
Required
Not required
DIMM
Type of air
blanks
shroud
Not
Standard
required
Not
Standard
required
Required
Not required
Required
Not required
Technical specifications
Fan
Four standard
fans and one
blank to cover
two fan slots
Six standard
fans
Six high
performance
fans
Six high
performance
fans
25