ensto PXA53 Instrukcja obsługi - Strona 16
Przeglądaj online lub pobierz pdf Instrukcja obsługi dla Akcesoria ensto PXA53. ensto PXA53 20 stron.
1. INTRODUCTION
The light fitting is designed for ceiling mounting. It can also be mounted on a wall at a height of
at least 1.7 m. The light will switch on automatically when a heat-emitting object such as a person
comes into its sensor's detection area. When choosing the place of installation avoid all interfering
sources within the detection area that might affect the light fitting's operation, such as ventilating
grates, warm air fans, reflective glass or wall surfaces, or other light fittings that are too close to the
PIR (Passive Infra Red) sensor.
Sunlight may also trigger the device if it appears suddenly within the sensor's detection area during
cloudy weather.
THE LIGHT FITTING SHOULD ONLY BE INSTALLED BY A PERSON WITH THE REQUISITE
KNOWLEDGE AND SKILLS.
USE ONLY THE BULB TYPE AND WATTAGE INDICATED ON THE LIGHT FITTING. THE PIR SENSOR
CANNOT CONTROL AN EXTERNAL LOAD EXCEEDING THE PERMITTED LEVEL!
TURN OFF THE POWER BEFORE MOUNTING OR REPAIRING THE UNIT.
KEEP THESE INSTALLATION INSTRUCTIONS FOR USE WHEN MOUNTING OR SERVICING THE
UNIT AT A FUTURE DATE.
Maximum external load: 400VA light fitting load.
Minimal illumination level (approx.5% or 20%) has already been set. This means that the light glows
dimly when the PIR sensor is not activated. The light intensity increases to 100% (80%) when the PIR
sensor responds to an object.
Minimum illumination level can be disconnect after 1 hour by changing parameter, see section 5. 1.
It´s possible also change min- level 5%
2. CONNECTION, see pic. 1
Connect the live wire to terminal L, the neutral wire to terminal N and the protection wire (yellow/ green
striped) to terminal
Light fittings can be connected in parallel. In single use. see pic. 1b.
WHEN MEASURING THE INSULATION RESISTANCE, THE POWER MUST BE SWITCED OFF. THE
NEUTRAL AND THE LIVE WIRES MUST BE CONNECTED TOGETHER.
THE INSULATION RESISTANCE IS MEASURED BETWEEN THE PROTECTION WIRE AND THE
CONNECTION OF THE NEUTRAL AND THE LIVE WIRES. TO ENSURE PROPER OPERATION THE
EARTH WIRE CONNECTION MUST BE SECURED.
3. DETECTION AREA, see pic. 2
The PIR sensor's detection area is 360° horizontally and approx. 135° vertically, as shown in pic. 2. The
detection distance depends on the height at which the sensor is mounted and the angle at which
movement occurs.
The sensor reacts most sensitively when movement occurs across its field of view and least sensitively
when movement occurs directly towards the sensor of the light fitting.
The detection distance may vary according to the ambient temperature. It may also vary if the distance
between the lens attached to the diffuser and the sensor in the light fitting has altered. The detection
area can be restricted to a desired direction by partially covering off the lens with the non-transparent
tape supplied in the kit.
16
. Connect the external load between connections
20% and/or max-level 100 %
80 %.
,
and N, (see pic. 1 a).