Entec LBS-751 Skrócona instrukcja obsługi - Strona 10

Przeglądaj online lub pobierz pdf Skrócona instrukcja obsługi dla Przełącznik Entec LBS-751. Entec LBS-751 12 stron. Electronic sectionalizer control

Entec LBS-751 Skrócona instrukcja obsługi
Quick Start Guide
LBS-751 Control
 
Analog Points
Special Analog Values 
Operations 
Phase PU (Amps) 
Ground PU (Amps) 
Trip Counter 
Control Points
Control Bits 
PB01 – Lock Push Buttons 
PB02 – Loop Mode Enable 
PB03 – CLOSE Switch 
PB04 – TRIP Switch 
Target Reset 
Trip Count Reset 
Reset Max / Min 
Polarity:
Logic 1 = Active Condition (Set Coil)
 
Modbus Protocol Codes
02h
Read Input Status (Coils) Command
Use function code 02h to read bits as individual coil values. The coil method increases data
size and may require multiple polls to completely read one device, but single binary values
placed in one coil greatly simplifies binary state determinations at the Scada master. Use
the 02h coil address provided in the status bit table above to collect data.
Bytes 
02h Read request format from Master 
1 byte 
1 byte 
2 bytes 
2 bytes 
2 bytes 
02h Successful response format from Slave 
1 byte 
1 byte 
1 byte 
n bytes 
2 bytes 
 
Source Location 
Tag 
Scaler 
MV01 
0.01 
MV02 
0.01 
MV03 
0.01 
SC03 
Source Location 
Tag 
Coil Address 
RB01 
27 
RB02 
28 
RB03 
29 
RB04 
30 
RB05 
31 
RB06 
32 
RB07 
33 
Field 
Slave Address 
Function Code (02h) 
Coil Address 
Number of coils to read (n) 
CRC‐16 
Slave Address 
Function Code (02h) 
Coils of data (n) 
Data 
CRC‐16 
10 
APPENDIX 2
03h Read 
User Table 
Address 
MOD_001 
126 
MOD_003 
128 
MOD_005 
130 
MOD_065 
190 
05h Force Single Coil 
Data Type 
Remote Bit Coil 
Remote Bit Coil 
Remote Bit Coil 
Remote Bit Coil 
Remote Bit Coil 
Remote Bit Coil 
Remote Bit Coil 
www.Entec-USA.com
Data Type 
32 Bit Signed 
32 Bit Signed 
32 Bit Signed 
16 Bit