Testing Ballast & Generator Capacitors.
WARNING: Dangerous voltage and/or current may be present when a
voltage test is being conducted. To reduce risk of serious injury or death from electrical
shock, if you are not trained to safely work with high voltage, do not attempt any of these
procedures. You must seek assistance from qualified personnel.
Disconnect both capacitor leads
Using a screwdriver or similar instrument with an insulated handle, short the capacitor
between the terminals to discharge any stored power (Figure B.1). The capacitor may
be freely handled after it has been discharged.
Select O hms o n your multimeter to t he highest setting.
Check the resistance between the capacitor terminals (Figure R.1).
A. If the meter shows a low resistance reading which gradually increases, the
capacitor is likely good and does not need to be replaced.
B. If the meter shows a very high resistance that remains steady, the capacitor is
open and must be replaced.
C. If the meter indicates a very low resistance that remains steady, the capacitor is
shorted and must be replaced.