Miele DA 292 i Instrukcja obsługi - Strona 23

Przeglądaj online lub pobierz pdf Instrukcja obsługi dla Okap wentylacyjny Miele DA 292 i. Miele DA 292 i 28 stron.

Miele DA 292 i Instrukcja obsługi
Air extraction
Push the ducting on to the cooker
hood exhaust connector or on to the
reducer (adaptor) and secure.
Note
If the exhaust ducting is to run through
rooms, ceiling space etc. where there
may be great variations in temperature
between the different areas, the prob-
lem of sweating or condensation will
need to be addressed.
The exhaust ducting will need to be
suitably insulated.
In addition to insulating the exhaust
ducting it may also be necessary in
some cases to install a suitable conden-
sate trap to collect and evaporate any
condensate which may occur.
When installing a condensate trap,
ensure that it is located vertically
and if possible directly above the
exhaust connection.
Calculation of extraction ducting
A pipe diameter of 125 mm (5'') should
ensure trouble-free extraction up to a
total pipe length of 33 m (108'').
Determine the total pipe length as fol-
lows:
Measure the total length of the ex-
haust ducting to be used.
Add the appropriate length of addi-
tional piping to this figure (see table),
according to the number and type of
bends:
Type
Angle
Radius of
of
of
bend
bend
in inch in mm in foot
Wall
vent
duct
with
grill
and
flap
Smooth
90°
5
interior
90°
10
wall
45°
5
bends
45°
10
Elbow
90°
bend
45°
Bend
90°
in
rent
hose
Flexible
90°
5
piping
90°
10
90°
20
45°
5
45°
10
45°
20
Air extraction
Length of
bend
additional
piping
metres
3,3'
125
1
250
3/4
125
3/4
250
1/2
6 3/4
1 3/4
2 1/2
125
1
250
1
500
3/4
125
3/4
250
3/4
500
1/2
in
1.0
0.3
0.2
0.2
0.1
2.0
0.5
0.7
0.35
0.3
0.2
0.2
0.15
0.1
23