ABB ACQ580-01 Series Instrukcja szybkiej instalacji i uruchomienia - Strona 10
Przeglądaj online lub pobierz pdf Instrukcja szybkiej instalacji i uruchomienia dla Urządzenia przemysłowe ABB ACQ580-01 Series. ABB ACQ580-01 Series 16 stron. Ul type 4x (ip66) drives, nec types
Również dla ABB ACQ580-01 Series: Podręcznik (16 strony), Instrukcja szybkiej instalacji i uruchomienia (17 strony), Instrukcja szybkiej instalacji i uruchomienia (17 strony)
parameters. To enable protection using motor model parameters or measurement devices set parameter 35.11 and
subsequent parameters through 35.55. To adjust motor class curves (default is class 20), change parameters 35.56 and
35.57.
?
Use the information key ( ) on the drive control panel for more information on setting group 35 parameters. You must set
the drive overload parameters correctly, or motor damage could occur.
Fieldbus communication
To configure the embedded fieldbus communication for Modbus RTU, you must set at least these parameters:
Parameter
20.01 Ext1 commands
22.11 Ext1 speed ref1
28.11 Ext1 frequency ref1
58.01 Protocol enable
58.03 Node address
58.04 Baud rate
58.05 Parity
58.06 Communication
control
Other parameters related to the fieldbus configuration:
58.14 Communication loss
action
58.15 Communication loss
mode
58.16 Communication loss
time
Setting
Description
Embedded
Selects fieldbus as the source for the start and stop commands when
fieldbus
EXT1 is selected as the active control location.
EFB ref1
Selects a reference received through the embedded fieldbus interface
as speed reference 1. Use this parameter with the vector motor control
mode.
EFB ref1
Selects a reference received through the embedded fieldbus interface
as frequency reference 1. Use this parameter with the frequency motor
control mode.
Modbus RTU
Initializes embedded fieldbus communication.
1 (default)
Node address. There must be no two nodes with the same node
address online.
19.2 kbps (default) Defines the communication speed of the link. Use the same setting as
in the master station.
8 EVEN 1 (default)
Selects the parity and stop bit setting. Use the same setting as in the
master station.
Refresh settings
Validates any changed EFB configuration settings. Use this after
changing any parameters in group 58.
58.17 Transmit delay
58.25 Control profile
58.26 EFB ref1 type
58.28 EFB act1 type
58.31 EFB act1 transparent
source
58.33 Addressing mode
58.34 Word order
58.101 Data I/O 1
...
58.114 Data I/O 14
10