4-9. Selecting Cable Sizes

.
ARC WELDING can cause Electromagnetic Interference.
To reduce possible interference, keep weld cables as short as possible, close together, and down low, such as on the floor.
Locate welding operation 100 meters from any sensitive electronic equipment. Be sure this welding machine is installed
and grounded according to this manual. If interference still occurs, the user must take extra measures such as moving
the welding machine, using shielded cables, using line filters, or shielding the work area.
!
Turn off power before
connecting to weld out-
put terminals.
put terminals.
!
!
Do not use worn, dam
Do not use worn, dam-
aged, undersized, or
poorly spliced cables.
poorly spliced cables.
*Weld cable size (AWG) is based on either a 4 volts or less drop or a current density of at least 300 circular mils per ampere. Contact your
2
distributor for the mm
equivalent weld cable sizes.

4-10. Connecting Weld Output Cables

Tools Needed:
3/4 in (19 mm)
!
Turn off power before connecting to
weld output terminals.
!
Failure to properly connect weld
cables may cause excessive heat
1
Weld Output Terminal
Total Cable (Copper) Length In Weld Circuit Not Exceeding
100 ft (30 m) Or Less
10 − 60%
Welding
60 − 100%
Duty
Amperes
Duty Cycle
Cycle
100
4
150
3
200
3
250
2
300
1
350
1/0
400
1/0
500
2/0
600
3/0
700
4/0
2-2/0
800
4/0
2-2/0
900
2-2/0
2-3/0
4
1
Do not place
anything between
weld cable terminal
and copper bar.
2
3
Correct Installation
2
Supplied Weld Output Terminal Nut
3
Weld Cable Terminal
4
Copper Bar
Remove supplied nut from weld output ter-
minal. Slide weld cable terminal onto weld
150 ft
200 ft
(45 m)
(60 m)
4
4
3
3
2
1
2
1
1/0
1
1/0
2/0
1/0
2/0
3/0
2/0
3/0
4/0
2/0
3/0
4/0
3/0
4/0
2-2/0
4/0
2-2/0
2-3/0
2-3/0
2-4/0
2-3/0
2-4/0
2-4/0
3-3/0
250 ft
300 ft
350 ft
(70 m)
(90 m)
(105 m)
10 − 100% Duty Cycle
2
1
1/0
1/0
2/0
3/0
2/0
3/0
4/0
3/0
4/0
2-2/0
4/0
2-2/0
2-3/0
2-2/0
2-3/0
2-3/0
2-2/0
2-3/0
2-4/0
2-3/0
2-4/0
3-3/0
2-4/0
3-3/0
3-4/0
3-3/0
3-4/0
3-4/0
3-4/0
3-4/0
4-4/0
3-4/0
4-4/0
4-4/0
Incorrect Installation
output terminal and secure with nut so that
weld cable terminal is tight against copper
bar. Do not place anything between weld
cable terminal and copper bar. Make
sure that the surfaces of the weld cable
terminal and copper bar are clean.
OM-228 470 Page 19
400 ft
(120 m)
1/0
3/0
4/0
2-2/0
2-3/0
2-4/0
2-4/0
3-3/0
3-4/0
4-4/0
4-4/0
S-0007-E
803 778-B