Temperature Readings and
Communication Errors
Temperature Sensor Readings is
Out of Reliable Measuring Range
• Low temperature readings:
Ambient temperature < -31°F/-35°C
• High temperature readings:
Ambient temperature > 91°F/35°C
Temperature Sensor is Not Connected
or Short Circuit
• "SensErr 2" Will appear on display.
• "SensErr" Will appear on display with
internal sensor fault
Slaves – Communication Error
Aux1 - Slaves Communication Error
•
"Aux1" and "00" Will appear on display.
2
Temperature
Sensor error
Slaves
communication
error
20
GFEP
The GFEP is designed to protect circuits
by sensing when a ground fault or
earth leakage is greater than 30mA and
automatically open the circuit.
The GFEP should be tested regularly, at
least once per month.
• Press TEST button "T", GFEP should open
automatically and the red indicator should
act.
• Move the handle back to "ON" position to
return to normal operation and reestablish
power and protection.
• Test button should be pressed 3 times and
the GFEP should work normally.
• If the GFEP is not operating normally, it must
be replaced.
"ON"
TEST
Handle
button
"TRIPPED"
Indicator
(red)