14. FOR ALL CABLES:
Strip 3/8 inch length of each conductor of the power cord.
Insert the bared ends of the conductors into the corresponding
openings on the unused side of the terminal block. Remember,
the green (ground) wire must be opposite of the opening of the
terminal block which is either empty or contains the metal
braid. See Figure 14.
Figure 14
15. FOR ALL CABLES:
Mount terminal block to bottom of the box by driving the 6/32
self-tapping screw into the mounting hole as shown. See
Figure 15.
Figure 15
16. FOR ALL CABLES:
Carefully push the wires into the box. Secure the lid to box.
See Figure 16.
INSTALLATION
#6/32 Screw
Limited Warranty:
Please refer to the Chromalox limited warranty applicable to this product at
http://www.chromalox.com/customer-service/policies/termsofsale.aspx.
1347 HEIL QUAKER BLVD., LAVERGNE, TN 37086
Phone: (615) 793-3900
17. FOR CABLE WITH EXPOSED METAL BRAID (-C):
Unravel four (4) inches of braid from the cable and twist into
a pigtail.
ELECTRIC SHOCK HAZARD. The twisted braid
must be effectively grounded in accordance with
the National Electrical Code to eliminate electric
shock hazard.
www.chromalox.com
Figure 16
Figure 17
SRL-C
or
CWM-C