Dictator RZ-24 Podręcznik techniczny - Strona 12
Przeglądaj online lub pobierz pdf Podręcznik techniczny dla Zasilanie Dictator RZ-24. Dictator RZ-24 19 stron. Central
Technical Manual
RZ-24 Central
Safe area
Central
unit
RZ-24
* Each ex-magnet has to be individually fused, with the fuse installed upstream of the magnet. You can find
more information in the manual of the magnets.
On site, the integration of a gas warning system must be checked by the ATEX representative on the basis of
explosion protection guidelines.
** Please refer to the Zener barrier manual for the detailed connection diagram.
Page 07.021.12
Electrical Connection and Installation of an Ex-Proof
Hold-Open System with RZ-24 - cont.
Fuse*
7
Zener barrier
Z779**
© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • Germany
Tel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 20220325
Hazardous area
zones 1 - 2
Max. 20 intrinsically safe
RM 3000IS EX smoke detectors or
WM 3000IS EX heat detectors
Screening, optional
(operational earth)
Up to 12 electromagnets
EM GD 50 EX or EM GD 70 EX
Ex-proof hand
release switch
700232
with resistor
3.9 kΩ
Ill. 5b