ABB LME620-AN Instrukcja obsługi - Strona 4
Przeglądaj online lub pobierz pdf Instrukcja obsługi dla Kontroler ABB LME620-AN. ABB LME620-AN 15 stron. Electrical linear actuators for continuous modulating control
5. Assemblies
4
7
6
5
4
Figure 1: LME 120 ...
5.1 Operation
5.2 Normal mode
The motor triggered by the electronics drives the axially fixed drive sleeve/nut assembly
via greased spur gears. A ball bearing screw radially fixed by an anti-twist arrester con-
verts the rotary to a linear motion.
The brake built in the motor acts as a retainer when the power is off.
The friction clutch is designed such that a handwheel force of around 11 N suffices to
create the rated torque on the actuator. If you should feel a considerable counter-force
when moving the actuator by hand, do not increase the force you apply to the hand-
wheel. Otherwise, you might damage the actuator or valve
5.3 Handwheel mode
- Allows you to move the actuator manually when the electrical power is off.
- Turn the handwheel lock lever clockwise to unlock the handwheel.
- Turn the handwheel to move the thrust rod to the desired position.
- Release the locking lever to lock the handwheel again.
7
2
1
3
d0042rxa
1: Handwheel
2: Handwheel lock
3: Thrust rod
4: Ext. stop
5. Gearbox
6. Connector plug
7. CSF
8. Cover
(for LME 620 AI incl.
electronics