clips See Figure 5.

FCC NOTICE

CAUTION: Changes or modifications not expressly approved could void your authority to use this equipment.
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful
interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment
generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will
be required to correct the interference at his own expense.
CAN ICES-005 (A)/NMB-005 (A)
Le présent appareil est conforme aux CNR d'Industrie Canada applicables aux appareils radio exempts de licence. L'exploitation est autorisée aux deux
conditions suivantes : (1) l'appareil ne doit pas produire de brouillage, et (2) l'utilisateur de l'appareil doit accepter tout brouillage radioélectrique subi,
même si le brouillage est susceptible d'en compromettre le fonctionnement.

ELECTRICAL CONNECTIONS

STEP 1:
NOTE: 347 Vac is a sperate sku
Make the following Electrical Connections:
a. Connect the black fixture lead to the line or Hot 1.
b. Connect the white fixture lead to the neutral or Hot 2.
c. Connect the green or green/yellow ground lead to ground.
d. If 0 -10 Vac Dimming is used, connect the violet lead to the supply
positive dimming lead. If dimming is not being used ensure to cap
off the violet lead.
e. If 0 -10 Vac Dimming is used, connect the grey or pink lead to
the supply negative dimming lead. If dimming is not being used
ensure to cap off the grey or pink lead.
f.
Secure incoming dimming leads to the existing strain relief, to
prevent contact with primary wiring.
© 2021 Cree Lighting, A company of IDEAL INDUSTRIES. All rights reserved. For informational purposes only. Content
is subject to change. See www.creelighting.com/warranty for warranty and specifications. Cree
registered trademarks of Cree, Inc.
Importer: IDEAL PRODUCTS DISTRIBUTION DE MEXICO S.
DE R.L. DE C.V.
Address: Paseo de los Adobes, 1079, no. 10, Colonia
Guadalajara Technology Park, C.P. 45010
Zapopan; Jalisco Mexico. TEL: +52 33 3627 7914
3 of 3
LINE
OR HOT 1
GREEN
NEUTRAL
OR HOT 2
VIOLET
GREY
OR PINK
®
and the Cree logo are
LUMINAIRE
LINE-BLACK
GROUND-GREEN
NEUTRAL-WHITE
DIM (+) VIOLET
DIM (-) GREY
OR PINK
www.creelighting.com