ABB Triguard SC300E Podręcznik użytkownika - Strona 4
Przeglądaj online lub pobierz pdf Podręcznik użytkownika dla Kontroler ABB Triguard SC300E. ABB Triguard SC300E 17 stron. 16-channel digital output module
Triguard SC300E
SPECIFICATION
Model
Channels
Architecture
Indicators:
Input
Modules
Output driver
Voltage range
Voltage drop
Maximum drive
Surge limiting
Isolation
Minimum load per output
Module power consumption excluding field
power dissipation in module
Module power consumption including field
power dissipation in module
Overall size (mm)
Overall size (inches)
Weight
ENVIRONMENTAL SPECIFICATIONS
The maximum ambient temperature measured at the hottest point within the Triguard system
shall not be greater than 60 degrees centigrade.
Temperature operating:
Temperature storage:
Humidity
EMC/RFI Immunity
Vibration/Shock
Certification:
General Certification: Ref. SC300E TMR Product Guide (ref 008-5209).
4
MDO16GNS
16
TMR
One per point
Health, 3 x On Line
FET
48Vdc ±10%
Less than 3V
Resistive load: 1A per channel
Tungsten load: 0.125A per channel
3A peak
1kVdc field to system, commoned supply
12mA (24mA if dual slot hot repair)
4W
6W @ minimum load
36W @ maximum load
400(9U)H x 397L x 28W
15.75H x 15.63L x 1.1W
2.1kg
+5°C to +60°C
-25°C to +70°C
5% to 95% non-condensing at ambient <40°C
Tested and certified to IEC 1131-Part 2 1994
Tested and certified to IEC 1131-Part 2 1994
MDO16GNS October 2005 – Issue 2