Siemens SIMATIC TP900 Comfort INOX PCT Kompaktowa instrukcja obsługi - Strona 44

Przeglądaj online lub pobierz pdf Kompaktowa instrukcja obsługi dla Urządzenia przemysłowe Siemens SIMATIC TP900 Comfort INOX PCT. Siemens SIMATIC TP900 Comfort INOX PCT 48 stron. Hmi devices; comfort panels
Również dla Siemens SIMATIC TP900 Comfort INOX PCT: Kompaktowa instrukcja obsługi (42 strony)

Siemens SIMATIC TP900 Comfort INOX PCT Kompaktowa instrukcja obsługi
Technical specifications
5.8 Technical specifications
Comfort HMI devices
Backlighting
Half Brightness Life Time (MTBF
Pixel error class in accordance with ISO 9241-307
Via WinCC: Complete value range, via Control Panel: Low limit up to 100
1
MTBF: Operating hours after which the maximum brightness is reduced by half compared to the original value. MTBF is
2
increased by using the integrated dimming function, for example, time-controlled via screen saver or centrally via
PROFIenergy.
Material
Component
Front frame
Front glass
Mounting gasket
Power supply
Comfort HMI devices
Rated voltage
Permitted voltage range
Rated current
Rated current, load-dependent
Inrush current I
t
2
Power consumption
1
Maximum permitted transient
Minimum time between two transients
Internal protection
The power loss generally corresponds to the specified value for power consumption.
1
See also
Notes on installation (Page 22)
44
)
2
Material
Stainless steel, material number 1.4301, V2A
Float glass, pre-stressed, toughened safety glass (ESG)
Shock-resistant according to EN62262 IK08 (5J, ball drop test)
anti-glare (Gloss 85) through disk etching
not surface-coated
safe (occupational safety): Fracture pattern defined at break: disinte-
gration into small glass particles (no sharp-edged fragments)
EPDM, 70 Shore A, black
TP900
Comfort
LED
80000 h
TP900
Comfort
24 V DC
+19.2 V to +28.8 V
0.75 A
0.75 ... 1.05 A
0.5 A
18 W
35 V (500 ms)
50 s
Compact Operating Instructions, 05/2018, A5E38804191-AA
TP1200
Comfort
I
TP1200
Comfort
0.85 A
0.85 A to 1.20 A
s
2
20 W
Yes
Comfort Panels INOX PCT