Application 2283 – Heating and/or
Chilled Water Cooling, ASHRAE Cycle III
In Application 2283, the Unit Vent Controller⎯0 to 10V Output controls a unit ventilator
equipped with a chilled water coil for cooling, and/or a heating coil, which may be hot water,
steam or electric, for ASHRAE Cycle III. A face-bypass damper can be controlled, replacing
both the modulating (0-10V) heating and cooling actuators. If a face-bypass damper is used,
two -position valves on the coils may be controlled. Heating only and cooling only units can
also be controlled with this application by overriding HEAT.COOL (Point 5).
Other features available in this application include morning warm-up/cool-down, night mode
override, free cooling, and auxiliary radiation in heating mode.
NOTE:
This application controls room temperature by directly modulating the coil control devices.
This application also controls an outdoor air damper according to the schedule as defined by
ASHRAE Cycle III, to maintain a given mixed air temperature setpoint. The free
cooling/economizer function is turned on and off by the field panel using FREE CLG (Point
23). If free cooling is not available, the outdoor air damper will be kept at minimum position;
otherwise, the outdoor air damper will modulate to maintain the mixed air temperature
setpoint. The unit ventilator fan is also controlled in this application.
Siemens Building Technologies, Inc.
The use of a low temperature detection thermostat (LTDT) is strongly
recommended for hot water and steam systems.
Figure 9. Application 2283 Control Drawing.
Application 2283 – Heating and/or
Chilled Water Cooling, ASHRAE Cycle III