Siemens 3WX3666-7JA00 Instrukcja obsługi - Strona 6

Przeglądaj online lub pobierz pdf Instrukcja obsługi dla Kontroler Siemens 3WX3666-7JA00. Siemens 3WX3666-7JA00 21 stron. Transfer control device

Block Diagram

Wiring
Notes
6
3 WN6 (QN)
Normal supply QN
3
Auxiliary supply
N
(L1, L2, L3)
connections
X100, X200
10 A
The wiring of terminal block X1 is shown in the following diagram:
Terminal block X1
L1
1
2
L2
3
L3
N
N
X100.9, X100.12, X200.2
N
4
X200.13
5
X100.8, X200.6
X200.7
6
7
X100.11
8
X200.8
9
10
X200.14
X200.3
11
X200.9
12
13
X200.12
• Ensure that the phase sequence of the feeders is correct.
• Use 10 A Diazed fuses for the feeders.
• Additional enable is possible via external switch on terminals 7 and 8 for switch-on of normal
mains supply. Remove the plug-in jumper in this case.
• Additional enable is possible via external switch on terminals 20 and 21 for switch-on of emer-
gency supply, e.g. for enable signal following generator start-up. Remove the plug-in jumper in
this case. Generator startup must be completed before giving switchover clearance.
Load
3 WN6 (QG)
Auxiliary supply
connections
X100, X200
3WX3666-7JA00
Terminal block X1
QN
Generator QG
G
3
(L1, L2, L3)
10 A
L1
14
15
L2
QG
16
L3
X100.9, X100.12, X200.2
N
17
X200.13
18
X100.8, X200.6
X200.7
19
20
X100.11
21
X200.8
22
23
X200.14
X200.3
24
X200.9
25
26
X200.12