ActronAir MGW-KNXCS Instrukcja obsługi - Strona 15

Przeglądaj online lub pobierz pdf Instrukcja obsługi dla Gateway ActronAir MGW-KNXCS. ActronAir MGW-KNXCS 16 stron. Vrf knx gateway

22: set Cool mode; data type: DPT_1.001 switch
Set value: 1-set as Cool mode
23: Set Heat mode; data type: DPT_1.001 switch
Set value: 1-set as Heat mode
24: Set Dry mode; data type: DPT_1.001 switch
Set value: 1-set as Dry mode
25: Set Fan mode; data type: DPT_1.001 switch
Set value: 1-set as Fan mode
26: Set mode +/-; data type: DPT_1.008 UpDown
Set value: 1-Down 0-UP
27: Set temperature +/- of Non Auto Mode; data type: DPT_1.008 UpDown
Set value: 1-Down 0-UP
28: The fan speed +/-;data type: DPT_1.008 UpDown
Set value: 1-Down 0-UP
29: Set cool temperature +/- of Auto Mode; data type: DPT_1.008 UpDown
Set value: 1-Down 0-UP
30: Set heat temperature +/- of Auto Mode; data type: DPT_1.008 UpDown
Set value: 1-Down 0-UP
11