Verifying the Securing Location

The RP, LC, and FC card slots are populated with filler cards.
Note
The card pallet contains the route processor cards (RPs), fabric cards (FCs), and line cards (LCs).
The Cisco NCS 4016 chassis is shipped in a double-wall carton on a standard shipping pallet. Always
transport the chassis in its original packaging and make sure that the system is transported and stored in
an upright position. If you plan to store system components before the installation, be sure to store the
components carefully and in their original shipping containers to prevent accidental damage.
Verifying the Securing Location
Before moving the chassis into position, make sure that you have properly prepared the site so that there
is sufficient room for installation and maintenance. Verifying the recommended space ensures that you
have enough space available to perform the initial installation of the chassis and its components.
The floor plan for the Cisco NCS 4016 chassis must include enough space to install the chassis in the
equipment rack and allow sufficient airflow for the system. The floor plan must also provide enough
room to access chassis components for maintenance (for example, to remove fan trays, power modules,
cables, and air filters).
For chassis installation, make sure that enough room exists in front of the chassis to accommodate
installation personnel and the lifting device used to hold the chassis in the rack while it is bolted to the
rack.

Front and Rear Clearances

The site requires the following front and rear clearances for chassis installation and maintenance access:
If the chassis in installed in a cabinet with doors, note the following restrictions:
Figure 1-1
Cisco Network Convergence System 4000 Series Unpacking, Moving, and Securing Guide
1-2
To install the chassis in the equipment rack: approximately 23.6 inches (60 cm)
To service components and allow system airflow in front of the chassis: 36 inches (91.4 cm)
To service components and allow system airflow behind the chassis: 24 inches (61 cm)
The chassis can be placed in a cabinet with the front and rear doors at least 80% open in front of the
inlet and exhaust openings of the chassis.
The distance between the inlet/exhaust and the door can be as small as 6 inches, but the door should
be facing to an open isle.
A foot of clearance at front and back should be maintained from the inlet/exhaust and a solid object.
shows the service area flooring in a lab from the top of the chassis.