Argina CM+ Instrukcja instalacji - Strona 11

Przeglądaj online lub pobierz pdf Instrukcja instalacji dla Jednostka sterująca Argina CM+. Argina CM+ 20 stron. Conventional fire alarm control panel

11.1 Connecting the integral operating panel

Hang the fire alarm control panel cover on the housing's lower pivot points.
Next plug the operating panel connector into one of the 3-pin connectors on the main PCB.
Ensure when closing the cover that the connecting cable is not trapped between the cover and
the housing.

11.2 Connecting external operating panels

Up to 2 external operating panels can be connected.
The wiring for external operating panels is 3-core.
The maximum length of 0.8 mm wiring is 50 m, and the maximum length of 1.5 mm
External operating panels are connected to the REPEATER terminals.
2
is 150 m.