Argo ADICS13DC Instrukcja instalacji - Strona 8

Przeglądaj online lub pobierz pdf Instrukcja instalacji dla Klimatyzator Argo ADICS13DC. Argo ADICS13DC 19 stron. Split air conditioner system
Również dla Argo ADICS13DC: Instrukcja obsługi (15 strony), Instrukcja obsługi (17 strony)

EN
Secure the unit in position with locknuts and
F
washers, level the unit, keeping the right distance
from the falseceiling for the installation of return air
grille.
The unit is supplied of PVC hose from the
H
condensate pump. Maximum pump lift is 250 mm
over the unit. Convoy the condensate with a positive
slop (min. 1:100) to the outside. The highest point
in the condensate pipework should be as close to
the unit as possible. This prevents a large volume of
water draining back into the unit when it is switched
off.
Predispose the terminals of the wire to connect to the terminal strip and connect them. (See electric wiring to
J
connect).
Secure inter-unit wire using the supplied clamp.
Loose wiring may cause the terminal to overheat or result in unit malfunction.
A fire hazard may also exist. Therefore, be sure all wiring is tightly connected.
When closing the electrical component box, take care not to leave part of the wires out or let them get
caught between the lid and the unit. Check to see that the tab is aligned, then tighten the screw.
WARNING
Predispose a removable panel of the falseceiling
G
for servicing.
Convoy the condensate to the outside with a
I
positive slope, from a trap at the end if necessary.
8