6-2.
7-2. Checking Continuity of Fuse
on PCB Ass'y
● Remove the PCB Ass'y from the electrical
component box. Then pull out the fuse from the PCB
Ass'y. (Fig. 5)
● Check for continuity using a multimeter as shown in
Fig. 6.
6-3.

7-3. Checking Motor Capacitor

Remove the lead wires from the capacitor terminals,
and then place a probe on the capacitor terminals as
shown in Fig. 7. Observe the deflection of the pointer,
setting the resistance measuring range of the
multimeter to the maximum value.
The capacitor is "good" if the pointer bounces to a
great extent and then gradually returns to its original
position.
The range of deflection and deflection time differ
according to the capacity of the capacitor.
Compressor motor
capacitor
18
Fuse
PCB Ass'y
Fuse
Multimeter
Fan motor
capacitor
Fig. 5
Fig. 6
Fig. 7