finder 19 Series Podręcznik - Strona 13

Przeglądaj online lub pobierz pdf Podręcznik dla Kontroler finder 19 Series. finder 19 Series 17 stron. Knx actuator

finder 19 Series Podręcznik

1.9 List of general configuration parameters (valid for each Channel)

Parameter
PAR_Value Force ALL Out
Forcing status of all Channels with highest priority
PAR_Enable Keyboard
Enable local keyboard for manual activation of Channels on test phase

1.10 Detailed description of the parameters of Channel configuration page

1.10.1 Par_Contact Type

Property Datatype: PDT_UNSIGNED_8bit
Datapoint Type: none
Range: 0÷1
It defines the contact type, normally open (NO = default) with the value 0, normally closed (NC) with the value
1. If the parameter is set to NO, the OFF state will correspond to relay/circuit open. If the parameter is set to NC
value in the OFF state will correspond to relay/circuit closed.

1.10.2 PAR_Startup

Property Datatype: PDT_UNSIGNED_8bit
Datapoint Type: none
Range: [0÷2]
It defines the channels condition at startup. Value 0 always select Off (default), value 1 always select On, value
2 after downloading the application the device will save the status of the channels at each change in a non-
volatile memory location (EEPROM), in order to recover it correctly at power-on. If the device has never been
programmed via the ETS, the state set will be the default value stored in EEPROM.

1.10.3 PAR_Function

Property Datatype: PDT_UNSIGNED_8bit
Datapoint Type: none
Range: [0÷5]
It defines the function associated with the channel in accordance with Table 3:
Value
Meaning
0
Switch On/Off
(default)
1
On delayed
2
Off delayed
3
Blinking
5
Stairs Light

1.10.4 PAR_On Delay (s)

Property Datatype: PDT_UNSIGNED_16bit
Datapoint Type: None
Range: [1÷65535]
It defines the waiting time in seconds from the reception of the DPT_Channel X Set ON/OFF = On message
before switching a channel in the ON status. Default value is 5. The maximum value is a waiting of about 18
hours.
FINDER SpA
which is the last channel status before power off or device reset. selecting value
Ver. 2018
Related parameters
None
PAR_On Delay (s)
PAR_Off Delay (s)
PAR_Blink On (s), PAR_Blink Off (s)
PAR_Stairs Light Time (s)
Table 3
KNX Actuator 19.6K
Default value
OFF
Yes
13