Lock pulse time set
Push and hold on OSC for the lock pulse time setting. Now the red and green LED flash fast
alternatively, and when gate reached the required time, simply release OSC button. Set DIP1 OFF.
The gate controller will back to working mode.
5.2 SPE(special) time setting mode
To get into special setting mode, turn power off, set DIP1 on. Push and hold CLS button then turn
power on, LED will be on for short time, after LED off simply release CLS button. Gate controller is
getting into special time setting mode.
Sync delay time (Motor2 delay time, reserved late use)
After controller get into special time setting mode, Push and hold on OPN for the sync delay time
setting. Now the red and green LED flash fast alternatively, when reached required time, simply
release OPN button. If no other time need set, simply set DIP1 off, the gate controller will back to
working mode.
Motor Stop time
Push and hold on PED for the motor stop time setting. Now the red and green LED flash fast
alternatively and when gate reached required time, simply release PED button.
PE trig close time
Push and hold on CLS for the PE trig close time setting. Now the red and green LED flash fast
alternatively and when gate reached required time, simply release CLS button.
Reserved
Push and hold OSC reserved late use.

5.3 Factory default setting

Timer
F/Setting
Full Open Length
10M
PED Open Length
5M
Auto Close Time
30sec.
Lock Pulse Time
0.8ec.
Motor Stop Time
1.0sec.
Sync Delay Time
Reserved
PE Auto close Time
2sec
Reserved
Reserved
To restore factory setting, turn power off and set DIP1 on, push and hold CLS button then
power on. While hold CLS button, set DIP1 off, release the CLS button. Now controller
restored factory setting from memory.
Attention: First time power up, the motor will run at low speed in close direction
(if DIP6 is on) and hit receiving post. Next open command gate will open at low
speed until to fully opened. The controller will calculate the gate length and
compare it with original gate length. If it is right, the gate will back to normal
operation, otherwise, gate will run at low speed.
DIGIWAY PTY LTD
CONTROL BOARD SETTING
Step
Setting Method
0.7mm
STD& OPN Button
0.7mm
STD& OPN+PED Button
0.1sec.
STD& PED Button
0.1sec.
STD& OSC Button
0.1sec.
SPE& OPN Button
0.1sec.
SPE& PED Button
0.1sec
SPE& CLS Button
0
SPE& OSC Button
7
Range
No limitation
No limitation
0-6550sec.
0-25sec.
0-25sec.
0-25sec.
0-25sec
0