Acuity Brands NaviLite N1L Instrukcje instalacji - Strona 3

Przeglądaj online lub pobierz pdf Instrukcje instalacji dla Oprawa oświetleniowa Acuity Brands NaviLite N1L. Acuity Brands NaviLite N1L 3 stron. For led emergency lighting fixture

FOR LED EMERGENCY LIGHTING FIXTURE
NOTE
1. Max mounting height 8 ft to achieve at least 1 ft-candle of illuminance in emergency mode.
OPERATION
1. During an electrical power failure, the LED lamps will automatically come on for a minimum of 90 minutes.
2. To test, depress the "TEST" switch. The emergency LED lamps will illuminate. When the switch is released, the
lamps will go off.
WIRING DIAGRAM
HO OPTION (REMOTE CAPABLE)
CHARGER
BOARD
AC INPUT CONNECTOR
(MOUNTING PLATE)
RED
277V
BLACK
120V
WHITE
0V
YELLOW(+)
BLUE(-)
YELLOW(+)
BLUE(-)
LAMP
YELLOW(+)
BLUE(-)
LAMP
TO REMOTE
READY
Note:
Use 18-22 AWG stranded
wire to connect remote lamp
heads.
©2016 Acuity Brands Lighting, Inc.
INSTALLATION INSTRUCTIONS
Note:
Unused input lead must
be properly insulated with
wire nut or other approved
method.
BLACK
TEST
One Lithonia Way, Conyers GA 30012
Printed in the USA Rev 8/2017
AC INPUT CONNECTOR
(MOUNTING PLATE)
RED
277V
BLACK
120V
WHITE
0V
LAMP
RED
LAMP
BATTERY
Phone: 800-334-8694
P3508
pg 3 of 3
STANDARD
CHARGER
BOARD
YELLOW(+)
BLUE(-)
YELLOW(+)
BLUE(-)
TEST
READY
RED
BLACK
BATTERY