Acuity Brands Lighting SPA Podręcznik - Strona 13

Przeglądaj online lub pobierz pdf Podręcznik dla Oświetlenie zewnętrzne Acuity Brands Lighting SPA. Acuity Brands Lighting SPA 18 stron.

Installation Instructions
RSX LED
4. Loosen the two cover screws of the SPA to access the pole mounting area (See Fig 17) and route supply wires through the
clearance slot and WBA cover hole.
5. Making sure that no wires are pinched, insert the 3/8" bolts (included with luminaire) through the mounting arm of the
fixture housing, through the cover plate, and then thread into the threaded steel bar (See Fig 18). Tighten the two bolts with a
9/16" socket to 20-30 ft-lbs (overtightening can damage components and void warranties).
6. Make sure no wires are pinched and tuck excess wire up into the luminaire mounting area and reinstall the SPA Cover that
was removed in step 3. Tighten the two cover screws with the 9/64 Allen wrench to 18-20 in-lbs (overtightening can cause
thread stripping and void all warranties).
CAUTION: THE NEXT STEPS WILL REQUIRE ASSISTANCE
7. Make all wiring connections via the supplied wire leads in accordance with NEC and local codes.
8. Place the entire light fixture/cover plate assembly onto the base plate (installed in step 1) and have someone tighten the top
(2) 3/8" x 1-1/4" stainless steel recessed hex set screws (See Fig 19) until 3/8" to 1/4" of the screw threads are still visible, then
tighten the bottom set screws.
9. Now, alternating between the top and bottom set screws, gently tighten until snug (approximately one thread will remain
showing on each screw).
©2016 Acuity Brands Lighting, Inc.
All Rights Reserved.
Lithonia Lighting Outdoor
One Lithonia Way, Conyers, GA 30012
Phone: 800-279-8041 Fax: 770-918-1209
www.lithonia.com
Part Number: IM-459 Rev A
Revision Date: 8/29/19
Page #11