2. Installation
- Use the Operator Panel within the operating ambient temperature range of 5 to 40
degC and operating ambient humidity range of 20 to 80%. The Operator Panel
may malfunction if it is used outside of these ranges. (The operating ambient
temperature range applies to both inside the panel and display screen side.)
Inside
Controller
Box
- Prevent the Operator Panel from overheating due to heat generated by other
equipment.
- The Operator Panel is designed for vertical installation. It can also be installed at
an angle. However, in this case, limit the angle of tilt from the vertical to 30 deg.
- If the Operator Panel is installed at an angle of tilt exceeding 30 deg, take
measures, such as forced air cooling, to prevent the operating ambient
temperature from exceeding 40 degC.
- Do not install the Operator Panel horizontally.
12
Outside
Controller
Box
Within 30deg.
OP1 Safety and Installation Rev.3