Float mechanism:
As soon as the pump is powered the digital display (5) shows 8. Press
the switch (6). The float will proceed through the following stages.
0. is displayed until the quantity of fuel has exceeded 1.3 litres.
1. the float is in the 3.5-litre reserve.
2. start of cycle. This digit is displayed until the end of the cycle.
3. end of cycle, the pump contains 7.3 litres.
Alarms :
4. low: level 1. not reached after 10 mins.
5. intermediate: level 2. not reached after 30 mins.
6. high: liquid in the drip tray.
7. temperature: temperature inside the pump is above 55°C.
8. In the event of breakdown:
Upon ignition, two failure warnings can appear on the display:
4. the pump may be running without liquid.
When 4. appears on the display, check the following points:
- The suction pipe is well screwed into the pipe fitting (air intake).
- The suction rod must be well inside the cistern.
- The filter is clean (cleaned once every year).
Check if, according to the table below (para.12), the maximum pipe
height or length has been exceeded
5. check that the entire installation is functioning properly.
When 5. appears on the display, check the following points:
- Check that the cistern is not empty.
- Check compression in the pipes.
- Check the points mentioned in the event of alarm 4.
When functioning, the pump has two safety devices:
6. drip tray safety device.
When 6. appears on the display, there has been a leak in the drip tray
(16).
Check the following points:
Check where the leak is coming from, whether the problem is the pipe
fittings (in/out), a cracked tray, or an overflow*. Before restarting the
pump, the drip tray must be emptied (loosen the four screws which are
found underneath the tray). * Be careful if the leak has been caused by
an overflow as this indicates that the pump did not stop upon reaching
the high level (point 3. upon ignition). Disconnect the plug (7), check that
the float is not blocked, then reignite.
7. safety device in the event of heightened temperature (fire, overhe-
ating etc...) Alarm 7. is displayed when the room temperature rises to
above 55°C. If this digit appears, check where the heat is coming from.
To restart the pump following each breakdown, it must be rebooted by
pressing the start button (6). If you have had to disconnect the pump
from the power source, commissioning will be required (see chapter 7).
9. For any unexpected incident:
- Pull out the plug (7).
- Close the shut-off valve (8).
- Advise after-sales service.
10. Maintenance:
For the pump to function efficiently, the filter should be cleaned annually.
The filter is visible once the lid (11) is removed. This filter can easily be
unscrewed using a coin. When reassembling, ensure that it is thoroughly
airtight
11. Guarantee:
The manufacturer grants 12 months' guarantee from the date of delivery.
Please keep a copy of the invoice and the warranty. This guarantee
applies to the parts that are faulty or are manufacturing defects, and is
limited to the replacement or the repair of the defective parts, without
entitlement to claim for compensation or damages. We cannot accept
responsibility in the event of improper installation, non-observance of the
specifications and maintenance not being carried out.
12. Important notice:
In the event that equipment has to be forwarded, the tank must be
correctly drained before sending. Damage caused by oil spillage during
transport is the responsibility of the sender.
13. Performance curves:
90
80
Flow SP32 02-80
70
60
50
40
30
20
10
0
0.00
1.00
14. WARNING:
The SP32 02 should be handled carefully. Installation and servicing must
be performed by trained / authorised personnel only and must confirm
with the requirements of the local building regulation. When fitting this oil
lifter outside, suitable weather proof protection should be provided.
In line with current UK guidance, when fitting this oil lifter inside a buil-
ding. it should be installed in a fire proof enclosure which is vented to
outside. This product must be installed in line with local regulations.
- 5 -
GB
2.00
3.00
4.00
5.00
Hauteur d'aspiration [m]
10m
20m
30m
40m
6.00
7.00