ABB SPAU 331 C Instrukcja obsługi i opis techniczny - Strona 10
Przeglądaj online lub pobierz pdf Instrukcja obsługi i opis techniczny dla Przekaźniki ABB SPAU 331 C. ABB SPAU 331 C 20 stron. Voltage relay
Configuration
switches
10
Part of the starting and tripping signals from
the relay modules are permanently connected
to the output relays, whereas part of the output
signals are routed through switchgroup SGR.
The switchgroup is located at the front edge of
the output relay module. The switches are set
through the opening in the relay system front
panel.
Switchgroup SGR on relay system panel
Switch Function
SGR/1 Tripping signal from stage U< to output relay A
SGR/2 Tripping signal from stage 3U<< to output relay A
SGR/3 Tripping signal from stage U
SGR/4 Tripping signal from stage U
SGR/5 Tripping signal from stage U< to output relay B
SGR/6 Tripping signal from stage 3U<< to output relay B
SGR/7 Starting signal from stage U< to output relay C
SGR/8 Starting signal from stage 3U<< to output relay D
Switchgroup SGB on PC-board in residual overvoltage relay module SPCU 1C6
Switch Function
SGB/1 Not in use
SGB/2 Not in use
SGB/3 Not in use
SGB/4 Blocking signal BS1 for blocking of U
SGB/5 Blocking signal BS1 for blocking of U
SGB/6 Not in use
SGB/7 Not in use
SGB/8 Not in use
Switchgroup SGB on PC-board in undervoltage relay module SPCU 3C15
Switch Function
SGB/1 Not in use
SGB/2 Not in use
SGB/3 Not in use
SGB/4 Blocking signal BS1 for blocking of U<-tripping
SGB/5 Blocking signal BS1 for blocking of 3U<<-tripping
SGB/6 Not in use
SGB/7 Not in use
SGB/8 Not in use
The switchgroups SGB on the PC-boards of the
relay modules SPCU 1C6 and SPCU 3C15 are
used for routing incoming external blocking sig-
nals to the protection stages to be blocked.
The functions of the switchgroups SGB and
SGR are described in the tables as follows:
> to output relay A
0
>> to output relay A
0
>-tripping
0
>>-tripping
0
Factory
setting
1
1
1
1
1
1
1
1
Factory
setting
0
0
0
0
0
0
0
0
Factory
setting
0
0
0
0
0
0
0
0