Fig. 3: Shielding cover
Fig. 4: Prevention to avoid
Fig. 5: Position of the sensor related
against direct solar
intrusion of humidity
with the filling point
2 - 5
radiation
6  .  e
lectrical connection
Electrical connection can only be made in a voltage - free state!
In the event that the level meter (sensor) is installed in an outdoor environment at a distance
greater than 20 m from the outdoor switchboard, or from an enclosed building, it is necessary
to supplement the electrical cable leading to the level meater (sensor) with suitable overvoltage
protection.
In the event of strong ambient electromagnetic interference, paralleling of conductors with power
distribution, or for distribution to distances over 30 m, we recommend using a shielded cable.
RFLS-53N-_-P-_
The source of the power voltage must comprise of a stabilised safe low power source with
galvanic separation. In the event that a switch-mode power supply is used, it is essential
that its construction effectively suppresses common mode interference on the secondary
side. In the event that the switch-mode power supply is equipped with a PE safety terminal,
it must be unconditionally grounded!
RFLS-53N-_-RE(SSR)-_
The device may only be connected to the power supply via an easy to reach switch with marked
turned off / on positions and must be protected by a fuse or circuit breaker with a value of max. 6 A!
The switch or circuit breaker used as the disconnect device must be in accordance with the
IEC60947-1 and IEC60947-3, must be marked and must not be in the network inlet.
RFLS-53N-_-RE(SSR)-_
The output wire of the device is not separated from hazardous circuits. It must not be connected
to secondary accessible safety circuits.