Ariston 200D Instrukcje instalacji, użytkowania i konserwacji - Strona 21

Przeglądaj online lub pobierz pdf Instrukcje instalacji, użytkowania i konserwacji dla Podgrzewacz wody Ariston 200D. Ariston 200D 33 stron. Heat pump water heater

Hysteresis value that allows the heat pump to restart
P9
HYST HP
after having achieved the target temperature. It can be
set by the installer in the [3 / 12°C] range.
This parameter gives the capacity of the tank; it is use-
P10
TANKVOL
ful in case of spare part customization.
Operation with PV:
0. OFF (PV disabled - default)
P11
PV MODE
1. PV_HP (PV with HP only)
2. PV_HE (PV with HP and HE1)
3. PV_HEHP (PV with HP and HE1 + HE2)
This parameter gives the temperature to be achieved
P12
PV TSET
in PV mode. It can be set by the installer in the [55 / 75
°C] range.
Operation with SG:
P13
SG MODE
0. OFF (SG disabled - default)
1. HP_ON (SG enabled with HP only)
System Operation:
0. STD (standard installation)
1. OUT (The product is configured to operate with a
coil auxiliary load controlled by the direct AUX con-
tact)
P14
SYSMODE
2. PRHE (The product is configured as a generator in
pre-heating to operate with an auxiliary load and
share the domestic hot water parameters)
3. SYS (The product is configured to operate with a coil
auxiliary load controlled via Bus)
P15
BUZZER
BUZZER beep at buttons pressure
Enable/disable the SILENT mode
P16
SILENT
ON (function enabled)
OFF (function disabled)
Restoring the factory settings
All the user settings will be reset to default values with
P18
FACT RS
the only exception of energy statistics, tank volume
and Wi-Fi (if present)
P19
MB SW
HP-TOP-MB software version as MM.mm.bb.
P20
HMI S
HP-MED-HMI software version as MM.mm.bb.
Gives the water temperature in °C read by the NTC
P21
T LOW
placed at low position in the water tank.
If the NTC is in error "-" is shown
Gives the water temperature in °C read by the NTC
P22
T HIGH
placed at high position in the water tank.
If the NTC is in error "-" is shown
Gives the water temperature in °C read by the NTC
P23
T DOME
placed at dome position in the water tank.
If the NTC is in error "-" is shown
Gives the air temperature in °C read by the NTC placed
P24
T AIR
on the outside unit.
If the NTC is in error "-" is shown
Gives the gas temperature in °C read by the NTC
P25
T EVAP
placed before the evaporator on the outside unit.
If the NTC is in error "-" is shown
Gives the gas temperature in °C read by the NTC
P26
T SUCT
placed before the compressor on the outside unit.
If the NTC is in error "-" is shown
Gives the gas temperature in °C read by the NTC
P27
T COND
placed after the condenser on the outside unit.
If the NTC is in error "-" is shown
Gives the gas temperature in °C read by the NTC
P28
T DISC
placed after the compressor on the outside unit.
If the NTC is in error "-" is shown
Gives the superheating temperature in °C. If the NTC
P29
T SH
evap or suction are in error "-" is shown
P30
ERRORS
Allows navigation among last 10 errors that occurred
The Wi-Fi function (if available) can be set to:
P31
WI-FISET
ON (function enabled)
OFF (function disabled)
Repetition every [1-30] days for the antibacterial cycle if
P32
F ANTB
active
P33
EBUS POWER ON (function enabled) - OFF (function disabled)
P34
HP-TYPE
Cascade setting [Master-Slave1,......Slave7]
• P11 PARAMETER - PHOTOVOLTAIC MODE "
If you have a photovoltaic system, you can set the product to op-
timise use of the electricity produced. After having done the elec-
trical connections as described in paragraph 4.11 fig. 14 and set the
P11 parameter to other than "0".
The signal should be received at least for 5 minutes to enable the
photovoltaic function (once the product starts a cycle, it will oper-
ate for at least 30 minutes).
When the signal is detected, the operating mode works as follow::
- OFF (value 0 – default)
PV mode disabled
- PV_HP (value 1)
When the signal from the inverter is present. The product will
reach the set temperature (the highest between T SET POINT
and PV TSET) with only the heat pump (max 62°C).
- PV HE (value 2)
The product will reach the set temperature (the highest between
T SET POINT and PV TSET) operating with only the heat pump
up to 62°C and if needed with the heating element (1500 W).
- PV_HEHP (value 3)
set temperature (the highest between T SET POINT and T W PV)
is achieved with the heat pump and the heating element (1000
W) up to 62°C. For higher Temeratures than 62 °C the second
heating element (1500 W) is activated.
• P13 PARAMETER - SG FUNCTION
If you have an SG signal, you can connect the signal cable as de-
scribed in the "electrical connections" chapter when the function
P13 is enabled the SG icon will be displayed.
Once the SIG2 signal has been received for at least 5 minutes
(once the product starts a cycle, it will work for at least 30 minutes),
the name of the selected mode alternates with the text SG ON and
the current operating mode is automatically changed by thermo-
stating the product at set temperature (the maximum between T
SET POINT and PV TSET), operating only with the heat pump (max
62 ° C).
• P16 PARAMETER - SILENT
This function reduces the sound level (performance can vary from
those declared). It can be enabled via the P16 parameter on the in-
staller's menu. Once activated, the symbol appears on the display
"
".

ANTI-FROST FUNCTION

If the temperature of the water in the tank falls below 5 °C while the
appliance is powered, the heating element (1000 W) will be automat-
ically activated to heat the water up to 16 °C.
DEFROST "
"
The defrost function is activated when the heat pump has been work-
ing for at least 20 minutes, the detected air temperature is below
15°C and the evaporator temperature is decreasing rapidly. When the
defrost cycle is running, the icon to the side is displayed.
"
21 / EN