Ariston 500 STD ProTech Instrukcje instalacji, serwisowania i obsługi - Strona 9

Przeglądaj online lub pobierz pdf Instrukcje instalacji, serwisowania i obsługi dla Podgrzewacz wody Ariston 500 STD ProTech. Ariston 500 STD ProTech 34 stron. Unvented hot water storage cylinders

3.8
Connection of Mains
Water Supply
For floor standing models:
On the front of the unit there is a label to identify the connection ports.
Please check this before making any connection to the unit.
For units up to 300 litres it is recommended that all mains cold water supply
pipe work is a minimum of 22mm, with the exception of model ST 50
ProTech where 15mm can be used. For 500 litre models the supply should
be 28mm. An isolating valve should be installed between the cold water
supply and the cylinder for servicing. ALL PIPEWORK MUST BE FLUSHED
TO AVOID DAMAGE TOTHE CONTROL VALVES.
Please refer to Figs. 3.1 - 3.7 for a suggested installation layout.
Draining taps must be located in acessible postions to permit the draining of
the whole cylinder. The taps must be a minimal size of at least 15mm
nominal size (preferably 22mm), and manufactured in accordance with BS
2879:1980.
When installing the expansion vessel it can either be connected directly to
the combination valve (see Figs 3.8 - 3.10), or it can be installed remotely
using the flexible hose supplied.
Important Note:-
When installing the expansion vessel, do not install the expansion vessel
vertically as air can become trapped in the expansion vessel resulting in
potential vibrations through the cylinder and pipework. When using the
flexible hose to remotely install the expansion vessel away from the control
valve, again, ensure that the vessel is not installed in a vertical position
where it can trap air.
See below for acceptable installation practices.