Aeotec ZWA005 Podręcznik - Strona 7

Przeglądaj online lub pobierz pdf Podręcznik dla Akcesoria Aeotec ZWA005. Aeotec ZWA005 8 stron. Trisensor

Aeotec ZWA005 Podręcznik
19)
Temperature Offset Value
The current measuring temperature value can be add and minus a value by this setting.
The scale can be decided by Parameter Number 20.
Temperature Offset Value = [Value] * 0.1(Celsius / Fahrenheit)
Parameter Number
30
20)
Light Intensity Offset Value
The current measuring light intensity value can be add and minus a value by this
setting.
Parameter Number
31
21)
Light Sensor Calibrated Coefficient
This configuration defines the calibrated scale for ambient light intensity. Because the
method and position that the sensor mounted and the cover of sensor will bring
measurement error, user can get more real light intensity by this parameter setting. User
should run the steps as blows for calibrating
1)
Set this parameter value to default (Assumes the sensor has been added in a Z-
Wave Network).
2)
Place a digital luxmeter close to sensor and keep the same direction, monitor the light
intensity value (Vm) which report to controller and record it. The same time user
should record the value (Vs) of luxmeter.
3)
The scale calibration formula: k = Vm / Vs.
4)
The value of k is then multiplied by 1024 and rounded to the nearest whole number.
5)
Set the value getting in 5) to this parameter, calibrate finished.
For example, Vm = 300, Vs =
2600, then k = 2600 / 300 =
8.6667
k = 8.6667 * 1024 = 8874.7 ≈ 8875
The parameter should be set to 8875.
Parameter Number
100
All Supports Command Class
This device supports Z-Wave Command Class as follows:
*
COMMAND_CLASS_ZWAVEPLUS_INFO
*
COMMAND_CLASS_SECURITY (V1)
*
COMMAND_CLASS_SECURITY_2 (V1)
*
COMMAND_CLASS_TRANSPORT_SERVICE (V2)
Size (Byte)
2
Size (Byte)
2
Size (Byte)
2
Available Settings
-200 ~ 200
Available Settings
-1000 ~ 1000
Available Settings
1~32767
(V2)
Default value
0
Default value
0
Default value
1024