ABB ACS580-01 drives Instrukcja szybkiej instalacji i uruchomienia - Strona 12

Przeglądaj online lub pobierz pdf Instrukcja szybkiej instalacji i uruchomienia dla Jednostka sterująca ABB ACS580-01 drives. ABB ACS580-01 drives 17 stron. Frequency converter. nec types
Również dla ABB ACS580-01 drives: Podręcznik (16 strony), Instrukcja szybkiej instalacji i uruchomienia (17 strony)

ABB ACS580-01 drives Instrukcja szybkiej instalacji i uruchomienia
Parameter
26.11 Torque ref1 source
28.11 Ext1 frequency ref1
58.01 Protocol enable
58.03 Node address
58.04 Baud rate
58.05 Parity
58.06 Communication control
Other parameters related to the fieldbus configuration:
58.14 Communication loss
action
58.15 Communication loss
mode
58.16 Communication loss
time

Warnings and faults

Warning
Fault
Aux. code
A2A1
2281
Current calibration
A2B1
2310
Overcurrent
A2B3
2330
Earth leakage
A2B4
2340
Short circuit
-
3130
Input phase loss
-
3181
Wiring or earth fault
A3A1
3210
DC link overvoltage
A3A2
3220
DC link undervoltage
-
3381
Output phase loss
-
5090
STO hardware failure
A5A0
5091
Safe torque off
A7CE
6681
EFB comm loss
A7C1
7510
FBA A communication
A7AB
-
Extension I/O
configuration failure
AFF6
-
Identification run
-
FA81
Safe torque off 1
-
FA82
Safe torque off 2
Ratings, fuses and typical power cable sizes
ACS580-
Nominal ratings
01-...
Input
Output
current
current
I
I
1
2
A
A
U
= 200...240 V, P
at U
= 3-phase 208/230 V, 60 Hz
1
n
n
04A6-2
4.6
4.6
06A6-2
6.6
6.6
07A5-2
7.5
7.5
10A6-2
10.6
10.6
017A-2
16.7
16.7
024A-2
24.2
24.2
031A-2
30.8
30.8
046A-2
46.2
46.2
059A-2
59.4
59.4
075A-2
74.8
74.8
088A-2
88.0
88.0
114A-2
114
114
143A-2
143
143
169A-2
169
169
211A-2
211
211
Setting
Description
EFB ref1
Selects a reference received through the embedded fieldbus interface
as torque reference 1. Use this parameter with the vector motor
control mode.
EFB ref1
Selects a reference received through the embedded fieldbus interface
as frequency reference 1. Use this parameter with the frequency motor
control mode.
Modbus RTU
Initializes embedded fieldbus communication.
1 (default)
Node address. There must be no two nodes with the same node
address online.
19.2 kbps (default) Defines the communication speed of the link. Use the same setting as
in the master station.
8 EVEN 1 (default)
Selects the parity and stop bit setting. Use the same setting as in the
master station.
Refresh settings
Validates any changed EFB configuration settings. Use this after
changing any parameters in group 58.
58.17 Transmit delay
58.25 Control profile
58.26 EFB ref1 type
Description
Warning: Current calibration is done at the next start.
Fault: Output phase current measurement fault.
The output current is more than the internal limit. This can also be caused by
an earth fault or phase loss.
A load unbalance that is typically caused by an earth fault in the motor or the
motor cable.
There is a short-circuit in the motor or the motor cable.
The intermediate DC circuit voltage oscillates due to missing input power
line phase.
Incorrect input and motor cable connection.
Intermediate DC circuit voltage is too high.
Intermediate DC circuit voltage is too low.
All three phases are not connected to the motor.
STO hardware diagnostics has detected hardware failure. Contact ABB.
The Safe torque off (STO) function is active.
Break in embedded fieldbus communication.
Communication lost between drive (or PLC) and fieldbus adapter.
The installed C-type module is not the same as configured, or there is an
error in the communication between the drive and module.
The motor ID run occurs at the next start.
The Safe torque off circuit 1 is broken.
The Safe torque off circuit 2 is broken.
Motor
gG fuse
1)
power
(IEC 60269)
P
n
ABB type
kW
hp
0.75
1.0
OFAF000H25
1.1
1.5
OFAF000H25
1.5
2.0
OFAF000H25
3.0
3.0
OFAF000H25
4.0
5.0
OFAF000H25
5.5
7.5
OFAF000H40
7.5
10.0
OFAF000H40
11.0
15.0
OFAF000H63
15
20
OFAF000H63
15
25
-
22
30
OFAF00H125
30
40
OFAF00H125
37
50
OFAF0H200
45
60
OFAF0H250
55
75
OFAF1H315
58.28 EFB act1 type
58.31 EFB act1 transparent
source
58.33 Addressing mode
3)
Fuses
uR/aR
UL class
2)4)
5)6)7)
fuse
T
(DIN 43620)
Bussmann type
170M1563
JJS-15
170M1563
JJS-15
170M1563
JJS-15
170M1563
JJS-15
170M1563
JJS-30
170M1565
JJS-40
170M1565
JJS-40
170M1566
JJS-80
170M1566
JJS-80
-
JJS-100
170M3815
JJS-150
170M3815
JJS-150
170M3817
JJS-200
170M5809
JJS-250
170M5810
JJS-300
58.34 Word order
58.101 Data I/O 1
...
58.114 Data I/O 14
Typical power cable sizes,
Cu
2 8)
9)
mm
AWG
3×1.5 + 1.5
14
3×1.5 + 1.5
14
3×1.5 + 1.5
14
3×1.5 + 1.5
14
3×2.5 + 2.5
10
3×4.0 + 4.0
8
3×6.0 + 6.0
8
3×10 + 10
6
3×10 + 10
4
-
3
3×35 + 16
2
3×50 + 25
1/0
3×70 + 35
3/0
3×95 + 50
4/0
3×120 + 70
300 MCM
12
Frame
size
R1
R1
R1
R1
R1
R2
R2
R3
R3
R4
R5
R5
R6
R7
R7