Excessive downtime cleaning could pulse dust from
unit out of incoming ducting.
1.3 OPERATION
1.1.1 CONTINUOUS CLEAN OPERATION
When using a Digital Pressure Monitor (DPM), or no
pressure gauge at all, SW2 on the timer board should
be set to CONTINUOUS CLEAN operation. Whenever
the blower is active, the system will continuously pulse
the cartridges. During continuous clean operation, the
CLEAN light will be illuminated.
1.1.2 PRESSURE SWITCH OPERATION
A separate pressure switch or Digital Pressure
Controller (DPC) isolated dry contact should be
supplied and wired to the PRESS SW terminals on TB3.
SW2 on the timer board should be set to PS (pressure
switch) operation. When the blower is active, the
system will pulse "On Demand" whenever the pressure
switch or DPC isolated dry contact is in the closed
position. The CLEAN light will be illuminated whenever
this dry contact is closed.
2
WA R N I N G
System Pulse Cleaning Operation
1.1.3 DOWNTIME CLEANING OPERATION
Upon motor/blower shutdown, downtime cleaning
can be performed in either pressure switch mode or
continuous clean mode. To perform downtime cleaning,
make certain the rotary switch labeled DT CYCLES is
set to the number of cycles desired (1 on the switch
indicates 1 cycle). During a downtime cleaning, the
CLEAN light will flash for the duration of the cycles
selected. The down time pulsing will begin 60 seconds
after the motorblower is turned off.
1.4 CONNECTION DIAGRAMS
Figure 1 shows the connection required for system
pulse cleaning operation. Notice the isolated normally
open motor starter auxiliary contact wired to the MOT
AUX terminals on the timer board. This is required for
either DPC, a DPM or no pressure gauge at all. When
using a DPM, make certain the SW2 is placed in the
CONTINUOUS CLEAN position. When using a DPC,
make certain SW2 is placed in the PS position.