Operation mode
40
41
Digital input
42
43
44
45
46
47
48
49
Set time & date
50
Factory reset
51
52
53
Back
54

MODBUS menu

Address
55
56
Baud rate
57
58
Parity
59
60
Back
61
Exit/save
MODBUS REGISTER
Pressure regulator MODBUS register.
Holding register
Register content
address
0
MODBUS address
1
Pressure
2
Mean pressure
3
Output voltage (V)
4
Temperature (°C)
5
Digital input 1
6
Digital input 2
7
Alarm relay
8
Setpoint
9
Manual setpoint
10
Temperature from MODBUS (°C)
11
Regulator speed
12
Output range low
13
Output range high
14
Operation mode
15
Mean operation mode
(Auto disabled after
10h)
Set operation mode
Regulator
Sensor 0+2000
Set D.IN function
DI1 function:
Motor alarm
Force setpoint
100 Pa
DI2 function:
Motor alarm
Force setpoint
100 Pa
Set time and date
Not available
Factory reset
Reset all settings?
No
Yes
Set MODBUS addr.
1
(1-247)
Set MODBUS baud
9600
rate
(9600, 19200...)
Set MODBUS parity
NONE
(NONE, EVEN,
ODD)
Value range
1 to 247
-200Pa to +2000Pa
-200Pa to +2000Pa
0-100(*1)
-300 to +700(*1)
0,1
0,1
0,1
0Pa to 2000Pa
0Pa to 2000Pa
-300 to +700(*1)
1-10
0-100%
0-100%
1-9(*2)
1-3(*3)
Automatically reset after 10 hours.
Pressure regulation function.
Pressure sensor function with 8 measurement
ranges.
Function selector for digital input 1.
Alarm function for fan motor thermal cut-out.
Alarm in the event of interruption.
Function for overriding a force setpoint. The over-
ride is not compensated for outdoor temperature.
Current override setpoint for digital input 1.
Function selector for digital input 2.
Alarm function for fan motor thermal cut-out.
Alarm in the event of interruption.
Other force setpoint function which is compen-
sated for outdoor temperature.
Current override setpoint for digital input 2.
Not available in this version.
Resetting CALAIR-PR-230V to factory settings.
Cancel resetting and return to Misc. Menu.
Complete reset to factory settings and return to
Misc. Menu. NB! Zero pressure calibration must
be carried out.
Back to main menu.
Current MODBUS address.
Settings range.
Current baud rate.
Settings range.
Current parity.
Settings range.
Back to main menu.
Return to normal display mode and save all
changes.
Read/Write
R
R
R
R
R
R
R
R
R
RW
RW
RW
RW
RW
RW
RW
7