Firetrol FTA1250 Series Instrukcja instalacji i konserwacji - Strona 11

Przeglądaj online lub pobierz pdf Instrukcja instalacji i konserwacji dla Kontroler Firetrol FTA1250 Series. Firetrol FTA1250 Series 18 stron. Markiii+ electric fire pump controllers

Firetrol FTA1250 Series Instrukcja instalacji i konserwacji
Choose the desired units of measurement for pressure reading and verify that it matches with the calibrated pressure
gauge installed on the sensing line. Set the Cut-In value according to your system specifications. Cut-Out value will
default to Cut-In plus 10 PSI. To manually enter the cut-out, select the check-box beside it and enter the desired
value (optional).
When finished, press the Service Done button. Any errors will be highlighted in red and, if forced, be logged in the
controller's event logs.
The "First Start up" is now completed. The controller is fully installed and configured.
11