FIREWOLF FW-RA-LED Okablowanie i instrukcje instalacji - Strona 3
Przeglądaj online lub pobierz pdf Okablowanie i instrukcje instalacji dla System bezpieczeństwa FIREWOLF FW-RA-LED. FIREWOLF FW-RA-LED 6 stron. Remote multiplex annunciator panels
CONTROLS & DISPLAYS:
For precise definitions of Control & Display operation, refer to the manual for the Fire Alarm Control Panel that the Annunciator
is being connected to.
Controls
System Reset, Signal Silence,
Buzzer Silence, Lamp Test.
WIRING INSTRUCTION:
The RS-485 Wiring to the FW-RA-LED Module is
recommended to be Twisted Shielded Pair as
shown in the diagram. The wire gauge may be;
22 AWG up to
2000 ft.
20 AWG up to
4000 ft.
18 AWG up to
8000 ft.
The RS-485 wiring from the Fire Alarm Control
Panel to the Annunciator(s) must be point-to-point
from the FA Panel to the first Annunciator, then the
next Annunciator, and so on. No star-wiring or T-
tapping is allowed. Each RAM-208 Annunciator
Module has a 120 ohm End-of-Line Resistor on
its RS-485 Output terminals. This is removed on
all except the last wired Module.
The 24 VDC field wiring needs to be of an
appropriate gauge for the number of annunciators
and the total wiring run length. See the
Specifications section "Current Drain for Battery
Calculations", and calculate the Maximum current
for all Annunciators summed together ...
NOTE: Accidentally connecting any of the 24
VDC wires to the RS-485 wiring could
result in damage to the Annunciator
and/or to the Fire Alarm Control Panel that it is connected to !!!
Maximum for
all Annunciators
Amperes
0.30
0.60
0.90
1.20
1.50
1.70
MAXIMUM WIRING RUN TO LAST ANNUNCIATOR
18AWG
16AWG
ft
m
ft
470
143
750
235
71
375
156
47
250
118
36
185
94
29
150
78
24
125
Displays
AC On, Common Trouble, Signal Silence,
8 Circuit Status LED's.
14AWG
m
ft
m
229
1200
366
114
600
183
76
400
122
56
300
91
46
240
73
38
200
61
3
MAX. LOOP
RESISTANCE
12AWG
ft
m
1900
579
850
259
570
174
425
129
343
105
285
87
Ohms
6
3
2
1.5
1.2
1.0