aerauliqa QR590E Instrukcja instalacji - Strona 13
Przeglądaj online lub pobierz pdf Instrukcja instalacji dla Wentylator aerauliqa QR590E. aerauliqa QR590E 20 stron. Energy recovery ventilation unit with enthalpic heat exchanger
Installer menu
6 Heating Threshold
7 Dehumidification
8 Speed Setting
9 Airflow Balancing
10 F7 filter
Installer menu
6 Heating Threshold
7 Dehumidification
8 Speed Setting
9 Airflow Balancing
10 F7 filter
Installer menu
6 Heating Threshold
7 Dehumidification
8 Speed Setting
9 Airflow Balancing
10 F7 filter
Installer menu
11 Filter Alarm interval
12 Working Hours Counter
13 Save settings
14 Load settings
15 Restore Default Settings
Installer menu
11 Filter Alarm interval
12 Working Hours Counter
13 Save settings
14 Load settings
15 Restore Default Settings
Installer menu
11 Filter Alarm interval
12 Working Hours Counter
13 Save settings
14 Load settings
15 Restore Default Settings
It allows to adjust the various speeds.
Press OK to enter.
Use or to choose speed 1, speed 2, speed 3 or Holiday.
Press OK to select.
The setting ranges are:
speed 1: 10% ÷ 80%
speed 2: 20% ÷ 90%
speed 3: 60% ÷ 100%
Holiday: 10% ÷ 40%
Use or to increase or decrease the speed percentage.
Press OK to select.
Press ESC to go back to the previous menu.
The factory settings (DEFAULT) are:
speed 1: 40%
speed 2: 70%
speed 3: 100%
Holiday: 20%
It allows to adjust the balancing of the two airflows.
Press OK to enter.
"Supply airflow" is highlighted.
Press OK to enter.
The setting range is: -20% ÷ +20%
Use or to adjust supply airflow against extract airflow
Press OK to select.
Press ESC to go back to the previous menu.
The factory settings (DEFAULT) is 0%
To be selected only in case an F7 filter is installed at the supply air side (Fig. 7.a).
Press OK to enter.
Use or to choose "Not installed" or "Installed".
Press OK to select.
The factory setting (DEFAULT) is "Installed".
It allows to set the Filter Alarm period: the system has a timer which activates the
"Filter" warning on the LCD at regular intervals.
Press OK to enter.
Use or to choose among 2-3-6 months or OFF.
Press OK to select.
The factory setting (DEFAULT) is 3 months if F7 filter is "Installed" or 6 months if F7
filter is "Not installed"
The system keeps trace of the actual working hours of the unit. This value cannot be
changed. Data is saved both on the motherboard and on the control panel CTRL-DSP,
to be safe in case of fault.
Press OK to enter.
Press OK or ESC to go back to the previous menu.
It allows to save the setting of the #1 (prototype) installation in the internal memory of
the CTRL-DSP to be loaded afterwards in other units.
Press OK to enter.
Use or to choose the position where to save hte setting. Up to 8 differrent
settings can be saved.
Press OK to select.
Press OK to confirm.
Press ESC to go back to the previous menu.
13