Acorn Safety S0704-PVD Instrukcja instalacji, obsługi i konserwacji - Strona 6
Przeglądaj online lub pobierz pdf Instrukcja instalacji, obsługi i konserwacji dla Urządzenia przemysłowe Acorn Safety S0704-PVD. Acorn Safety S0704-PVD 8 stron. Drench hoses
Installation & Operation Manual
S0704
-PDM
OPERATION INSTRUCTIONS:
Employees who work with hazardous materials should
become familiar with the location and operation of the
nearest emergency plumbing fixture. Emergency plumbing
fixtures stations are simple to use and require hands free
operation once the station is activated. Regular instruction
regarding proper care and use will increase confidence that
the units are accessible and function properly.
The route and area surrounding the Eye Wash should be
clear and unobstructed; the sooner eyes are flushed, the less
likelihood of damage. Eye Wash stations should be located in
close proximity to the hazard and take no more than 10
seconds to reach. In the case of sever eye contamination the
victim may require assistance to the Eye Wash station and
help flushing their eyes.
Safety plumbing fixture equipment should be operated
weekly for a period long enough to verify operation, clear the
supply line of any sediment build-up and minimize microbial
contamination due to sitting water.
1. To start the Drench Hose, push down on actuator. Flushing
should start, popping the spray nozzle caps open.
2. Lower both eyes into flow. Both eyes should be flushed to
prevent contamination from one eye from being delivered
to unaffected eye. Personnel who wear contact lenses
should remove them immediately prior to or during the
flush to prevent the contamination from remaining against
the cornea possibly causing unnecessary damage or pain.
3. Using thumb and forefingers, fully open eyelids and flush
eyes thoroughly for approximately 15 minutes or until
medical personnel arrive. Be prepared to let the doctor
know what type of contamination has entered the eye.
4. When finished pull up on actuator completely to standby
position. Flushing fluid should stop. Once flushing fluid has
stopped flowing, return spray nozzle lids to the closed
position to protect from airborne contaminates.
S0704-PDM MAINTENANCE GUIDE:
Maintain and inspect in accordance with ANSI Z358.1-2009
1. Check for obvious signs of wear, broken or defective
equipment. Re-paint if necessary. Replace missing or
defective equipment such as broken push paddles,
missing signs and inspection tags.
2. Remove strainer and washout any debris collected
–replace as required.
3. Operate drench hose nozzles pushing the actuator to
place ball valve in the fully "ON" position checking for
smooth operation of valve push paddle mechanism at the
same time ensuring that the drench hose spray nozzle
caps pop off immediately when actuated. If the ball valve
does not operate smoothly check the actuating assembly
for binding or missing parts. If the drench hose spray
nozzle caps do not pop off immediately when actuated
check for correct supply inlet pressure.
4. While in operation, inspect spray nozzles for clogs or
debris correct or replace as required.
Acorn Safety
a division of Acorn Engineering
Manual #7109-508-001
5. Return push paddle to vertical or fully "OFF" position
and swing back to stand by position. To prevent
drench hose spray nozzles from becoming
contaminated, always close nozzle lids after each
use.
Company
™
Page 6 of 8
Date: 03/28/13