Distech LonWorks ECL-203 Series Instrukcja instalacji - Strona 7

Przeglądaj online lub pobierz pdf Instrukcja instalacji dla Kontroler Distech LonWorks ECL-203 Series. Distech LonWorks ECL-203 Series 17 stron.

Distech LonWorks ECL-203 Series Instrukcja instalacji

Input Wiring

Before connecting a sensor to the controller, refer to the installation guide of the equipment manufacturer.
£
For a wire length less than 75' (23m), either a shielded or unshielded 18AWG wire may be used.
£
For a wire up to 200' (61m) long, a shielded 18AWG wire is recommended.
£
The shield of the wire should be grounded on the controller side only and shield length should be kept as short as possible.
Table 1 shows the ECL-203, ECL-300, ECL-400, and ECL-600 Series controller pulse and current input jumper support. Table 2 shows the available uni-
versal input (UIx) wiring methods.
Controller
ECB‑203
ECB‑300
ECB-400 Series
ECB-600 Series
£
Dry Contact input.
£
RTD input (for example, 1000Ω).
£
Thermistor Input (for example, 10kΩ type II and III).
£
Resistive input, (for example, use with 10kΩ and 100kΩ potentiometers).
ECL-203 Series:
£
0 to 20mA input used with a 2-wire, 0 to 20mA sensor powered by the controller's internal
15VDC power supply.
ECL-203 Series:
£
0 to 20mA input used with a 2-wire, 0 to 20mA sensor powered by an external 24VDC
power supply.
ECL-203 Series:
£
0 to 20mA input used with a 3-wire, 0 to 20mA sensor powered by an external 24VAC
power supply.
ECL-203 Series:
£
0 to 20mA input used with a sensor powered by its own power source.
Fast and Slow Pulse Inputs support
50Hz: 10ms minimum ON/OFF
(Fast Pulse)
None
UI1 to UI4
UI1 to UI4
UI1 to UI4
Table 1: Controller Input Support
Sensor Input Type
1Hz: 500ms minimum ON/OFF
(Slow Pulse)
UI1 to UI6
UI5 to UI10
UI5 to UI12
UI5 to UI16
Digital Dry Contact
Thermistor
Sensor
0-20mA
Sensor
0-20mA
Sensor
0-20mA
Sensor
Current Input Jumper support:
0 to 10VDC / 0 to 20mA
None
Yes; see Table 2
Input Connection Diagram
UIx
NO-NC
COM
UIx
RTD/
COM
Potentiometer
UIx
10kΩ
COM
+15VDC
+
To Controller's
UIx
0-20mA
Analog-To-Digital
COM
249Ω / ¼W
249Ω ¼W
UIx
-
+
COM
24VDC
249Ω ¼W
UIx
+
Common
COM
24VAC
AC
249Ω ¼W
UIx
+
-
COM
7 / 16
To Digital
Input
To Analog-
To-Digital
Converter
To Analog-
To-Digital
Converter
Converter
To Analog-
To-Digital
Converter
To Analog-
To-Digital
Converter
To Analog-
To-Digital
Converter