esera automation Auto-E-Connect 11230 Podręcznik użytkownika - Strona 2
Przeglądaj online lub pobierz pdf Podręcznik użytkownika dla Systemy wejścia/wyjścia esera automation Auto-E-Connect 11230. esera automation Auto-E-Connect 11230 6 stron. 4-fold analog input insulated for 1-wire bus
4
Technical data
Analog inputs:
Resolution:
Number of input channels:
Measuring range:
Max. input voltage:
Insulation:
Insulation strength:
Input impedance:
Input filter:
1-Wire Interface:
1-Wire function:
Interface:
Operating voltage:
Current consumption
Display:
Connection:
Note: A 12V supply voltage is required to operate the module. Recommended is the use of one of our 1-Wire
Hub III or Hub IV devices.
5
Ambient conditions
Temperature, operation: -20°C to +60°C
Humidity:
Dimensions:
Protection class:
Protection type:
6
Connection plan
Connection module top side:
Analog input
7 + 8 = minus input (internally connected)
9 = Plus input 1
10 = Plus input 2
11 = Plus input 3
12 = Plus input 4
Note:
Minus inputs Pin 7 + 8 interconnected.
Module bottom side:
1-Wire bus
1 = GND (ground)
2 = 1-Wire
3 = +12V voltage
4, 5 + 6 = no function
Note:
Do not connect the GND/ground of the
1-Wire Bus to the minus inputs.
All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of
ESERA GmbH. Errors and technical modification subject to change. ESERA GmbH, ESERA-Automation 2020
www.esera.de
Resolution 12Bit fix, ca. 3mV
4 x analog input 0-10VDC
0 - 10VDC
12V (overvoltage protection)
Isolation of the input section from the 1-Wire bus.
All analog inputs have a common ground potential.
Minimum 500VAC
200 KOhm
Cut-off frequency 0,5 Hz
Control via DS2450 commands
1-Wire bus insulated (5V, 12V, data and load)
12V= (+/-10%)
Ca. 20mA/12V (all inputs to 100% measuring range)
Green LED indicator for power supply
Screw terminals (up to 2.5qmm cable cross-section)
10 - 92% (non-condensing)
Housing 35 x 90mm
III
IP20
11230 V2.0 R1.0 Manual
Page 2 of 6