Recommended lifting method
1. Safety slings
TSU 95C - TSU 1050C: H= 2160 mm
TSU 790D – TSU 1440D: H= 2415 mm
THE LIFTING CABLES MUST BE VERTICAL IN BOTH PLANES AS SHOWN.
WHEN LIFTING UNITS AS SHOWN, SOME TANK COVERS MUST BE REMOVED TO PROVIDE
ACCESS TO THE LIFTING EARS. ENSURE THAT THE LIFTING CABLES DO NOT DAMAGE THE
Three lifting beams are required. The lifting ears and tank are not designed to support the loads resulting from lifts
employing less than 3 lifting beams as shown in hereunder.
Lifting methods not permitted
2 Rigging
2 Rigging
Caution
Caution
REMAINING COVERS.
W W W . B A L T I M O R E A I R C O I L . E U
11