CONTROL OF EVAPORATOR FANS FOR SECTION 2

Section 2 has 1 relay to control evaporator fan (26-27)
The fan control mode is selected by means of the "FnC2" parameter:
FnC2=C-n
fans will switch ON and OFF with the compressor 2and not run during defrost:;
FnC2= O-n
fans will run continuously, but not during defrost
After defrost, there is a timed fan delay allowing for drip time, set by means of the "Fnd2" parameter.
FnC1=C-y
fans will switch ON and OFF with the compressor 2 and run during defrost;
FnC1=O-y
fans will run continuously also during defrost
An additional parameter "FSt2" provides the setting of temperature, detected by the evaporator probe 2, above which the fans are always OFF. This
can be used to make sure circulation of air only if his temperature is lower than set in "FSt2".
7.

DISPLAY

1.3 THE KEYBOARD
To display and modify target set point 1. During programming it selects a parameter or it confirms a value.
To display and modify target set point 2
in programming mode it browses the parameter codes or decreases the displayed value. By holding it pressed for 3s the defrost for
section 1 is started
In programming mode it browses the parameter codes or increases the displayed value. By holding it pressed for 3s the defrost for
section 2 is started
It activates light 1
It activates light 2
Section 1 Stand-by
Section 2 Stand-by
KEYS COMBINATIONS