Przeglądaj online lub pobierz pdf Instrukcja instalacji i obsługi dla Jednostka sterująca dixell XJ200. dixell XJ200 3 stron. Communication module
Connect the white connector to the "+5V supply" connector of the PW-200J.
Connect the other devices to the RS485 serial line in compliance with the polarity.
Use the disconnecting terminal supplied with the PW-200J as a bridge of the RS485 line
with the XJ200 as follows:
Connect the GREEN wire of the XJ200 to the RS485 "+" terminal.
Connect the PINK wire of the XJ200 to the RS485 "-" terminal.
7.2 DEVICE EQUIPPED WITH A TTL SERIAL OUTPUT
7.2.1 Device with a TTL output but not able to power the XJ200.
E.G. Ranges: Prime CX, Wing Basic New, XC400C and XC600C
XJ200 and PW-200J connection
Connect the GREEN wire to the RS485 "+" terminal of the PW-200J.
Connect the PINK wire to the RS485 "-" terminal of the PW-200J.
Connect the white connector to the "+5V supply" connector of the PW-200J.
Controller connection with TTL and PW-200J
Connect the other devices to the RS485 serial line in compliance with the polarity.
Connect the 2 TTL outputs of the PW200J and the device.
Then connect the RS485 line to the PW200J, in compliance with the polarity.
8. CHECK OF GOOD CONNECTION QUALITY BETWEEN THE XJ200
MASTER AND THE OTHER XJ200 OF THE NETWORK
The following must be implemented in order to verify good connection quality between
an XJ200 and the master connected to the X-WEB:
1.
Connect and power the XJ200 Master to the X-WEB
2.
Set the XJ200 in place where it is to be installed
3.
Power the XJ200 and press the LED Power button for a couple of seconds
4.
A test cycle begins and lasts a few minutes
5.
At the end of the cycle, the following remains on:
a.
Good communication: the GREEN "RADIO" LED is on
b.
Insufficient communication: the YELLOW "RS485" LED is on; in this case,
try installing the XJ200 in a better position or connect another XJ200
between the Master and the XJ200 being tested.
1592010320 XJ200 GB r1 3 24 10 2014-FCC
9. TECHNICAL DATA
Operating Frequency:
Europe version: XJ200 -00000: 869.4 - 869.650 MHz
AUS and USA version: XJ200 -10000: 906 - 924 MHz multi channel (*)
(*) the channel selection must be done through one of the DIXELL approved
tools.
Container: Self-extinguishing ABS
Format: Front panel 80 x 80 mm; depth 5 mm
Power Supply:
XJ200 +5Vdc (from the controller or from the PW-200J module)
Note: the PW200J feeder or any Dixell controllers that can power the XJ200 are SELV-
type. Max Power <18VA, DC current < 8A.
Power Consumption: 0.30 VA max.
Operating Temperature: from 0 to 60 °C
Storage Temperature: -25 to 60
Relative Humidity: 20 - 85% (no condensation)
The XJ200 -00000 is compliant with the following standards:
ETSI EN 300 220-2 V2.1.2 (2007-06)
ETSI EN 301 489-3 V1.4.1 (2002-08)
CEI EN 60950-1 (2007-02)
It therefore meets the essential requirements of the following Directives:
Radio and telecommunications terminal equipment 99/5/EC
Electromagnetic compatibility 2004/108/EC
Low Voltage equipment 2006/95/EC
The XJ200 -10000 (906 - 924 MHz) is compliant with the following standards:
AS/NZS 4268: 2008:
Classification: Schedule 1: Item 45
FCC 15.247
The XJ200 -10000 (906 - 924 MHz) is compliant to Part 15 of the FCC Rules:
Operation is subject to the following two conditions:
(1) this device may not cause harmful interference, and
(2) this device must accept any interference received, including interference that may
cause undesired operation."
Unauthorized repairs, changes or modifications could result in permanent damage to the
equipment and void your warranty and your authority to operate this device under Part
15 of the FCC Rules.
NOTE: This equipment has been tested and found to comply with the limits for a Class A
digital device, pursuant to part 15 of the FCC Rules. These limits are designed to
provide reasonable protection against harmful interference when the equipment is
operated in a commercial environment. This equipment generates, uses, and can
radiate radio frequency energy and, if not installed and used in accordance with the
instruction manual, may cause harmful interference to radio communications. Operation
of this equipment in a residential area is likely to cause harmful interference in which
case the user will be required to correct the interference at his own expense.
The XJ200 -10000 (906 - 924 MHz) is compliant to RSS 102
Cet XJ200 -10000 (906 - 924 MHz) instrument répond aux normes RSS 102
This device complies with Industry Canada RSS-210. Operation is subject to the
following two conditions: (1) this device may not cause interference, and (2) this device
must accept any interference, including interference that may cause undesired operation
of the device.
Le présent appareil est conforme aux CNR d'Industrie Canada applicables aux appareils
radio RSS-210. L'exploitation est autorisée aux deux conditions suivantes : (1) l'appareil
ne doit pas produire de brouillage, et (2) l'utilisateur de l'appareil doit accepter tout
brouillage radioélectrique subi, même si le brouillage est susceptible d'en compromettre