Installation and Operation Instructions
Electronic Digital Thermometer with
maximum / minimum temperature log
XT11S
1.
GENERAL WARNING
PLEASE READ BEFORE USING THIS
MANUAL
 This manual is part of the product and shall be kept near
the device for easy and quick reference.
 Check the application limits before proceeding.
SAFETY PRECAUTIONS
 Always ensure that the probe is connected to the
instrument before the power supply is connected and
turned ON.
 Check the supply voltage is correct before connecting the
instrument.
 The probe is NOT protected as a low voltage circuit
on models with 230V or 110V power supply. (12 volt
with a power transformer should be used in
applications where liquids may be a concern.)
 The instrument is designed for panel mounting and
electrical connections must be positioned inside a properly
protected enclosure/panel.
 Do not expose to water or moisture: use the instrument
only within the operating limits avoiding sudden
temperature changes with high atmospheric humidity to
prevent condensation formation.
 Warning: disconnect all electrical connections before any
kind of maintenance.
 The instrument shall never be opened.
 In case of failure or faulty operation send the instrument
back to the retailer or to "Dixell S.r.l." (See address) with a
detailed description of the fault.
 Assure that the wires for probes and for power supply are
separated and far enough from each other, without
crossing or spirals.
2.
GENERAL DESCRIPTION
The XT11S is an electronic digital thermometer which
displays the current temperature and logs the maximum and
minimum temperatures experienced.
The maximum/ minimum temperatures can be displayed at
the touch of a button and reset if required. (Requires an
additional switch)
3.
INSTALLATION 230V OR 115V (FIG.1)
The instrument is equipped with fast-on type spade terminals
with probe connections separated from the power supply
connections. To install the instrument proceed as follows:
WeissInstruments_XT11S_05152013_mm
1.
Make a 59x25.5 mm (1.01"x2.32") hole in a panel with
maximum thickness of 2.7mm.
2.
Take the instrument from the box and place it in the
hole until the side flaps click, which means they are
locked.
3.
Disconnect the power supply from the board by
means of the panel switch (P1 in Fig.1)
4.
Place the probe where it has to measure the
temperature.
5.
Connect the probe terminals to the 2.8mm (.110") fast-
ons as indicated.
6.
Connect the power supply cables to the 6.3mm (.25")
fast-ons.
7.
If possible, the manufacturer suggests connecting the
phase (L) to the fast-on on the right and neutral (N) to
the fast-on on the left as indicated.
8.
At this stage the board can be connected to the power
supply once more.
Probe
Power Supply
input
°C/°F
(N)
P1
(N)
Line
(L)
Fig.1
4.
PROBE SUBSTITUTION (FIG.1)
1.
Disconnect the power supply on the board
where the instrument is positioned, by means of
the panel switch (P1 in Fig.1)
2. Remove the power supply spade-on.
3. Disconnect the instrument and the probe.
5.
°C/°F CHANGE
Use the black jumper to change from °C to °F and vice
versa. With the jumper closed the °F values are displayed,
without jumper the °C values are displayed.
6.
EXTERNAL PUSH-BUTTON
CONNECTION TO DISPLAY MIN/MAX LOGGED
TEMPS (FIG.2)
In order to display the maximum and minimum values on the
instrument, use the S1 Class II approved type push button,
normally open. (NOT SUPPLIED). ORDER P/N: PB-KIT
1.
Before carrying out the connections, disconnect the
power supply on the board where the instrument is
positioned.
2.
Connect the push button in parallel with the probe as
shown in Fig.2.
Probe
0
input
°C/°F
-10°C
+10°C
-17°F
+17°F
S1
Probe
Fig.2
(L)
7.
DISPLAY OF MINIMUM & MAXIMUM
TEMPERATURE LOGGED
Fuse
Once the button for minimum & maximum temperature
63mA
display has been connected, proceed as follows:
Maximum temperature display:
1.
Press and hold the push button (S1) until the display
reads "HI".
2.
Release S1 and the highest temperature recorded
since the last reset will be displayed for 3 seconds.
Minimum temperature display:
1.
Press and hold the push button (S1) until the display
reads "LO".
2.
Release (S1) and the lowest temperature recorded
since the last reset will be displayed for 3 seconds.
Probe offset value display:
1.
Press and hold the push button (S1) until the display
reads "PO".
2.
Release S1 and the probe offset value will be displayed
for 3 seconds.
Maximum /minimum temperature reset
1.
Press and hold the push button (S1) until the display
reads "rE".
2.
Release S1 and the display will flash "rE" for 5 seconds.
3.
While the display is flashing press the push button and
the max & min temperature will be erased.
Power on and power failure warning:
XT11S
When the power supply is turned on and after any power
failure, when the maximum and minimum set values are
visualised, the display flashes. This is to warn the user that
there has been an interruption to the power supply.
To restore normal operation, follow the same procedure that
is used for re-setting the maximum/minimum memory. (See
Maximum /minimum temperature reset).
8.
MAINTENANCE AND CLEANING
Instruments do not require particular maintenance. To clean
frontal frame, just use a soft moist cloth and avoid using any
strong detergent or solvent.
9.
TECHNICAL DATA
Case: 64x31mm, depth: 19.5mm; self extinguishing
Power Supply
polycarbonate (ULV2)
Mounting: only for panel mounting; 25.5x59mm panel cut
out (1.01"x2.32")
Frontal protection: IP65
Electrical connections: fast-on type spade terminals with
probe connections (2.8mm/ .110") separated from
S1: external
power supply connections (6.3mm/ .25").
push button
Power supply: 230Vac ±10% 50/60Hz or 110Vac ±10%
50/60Hz or 12Vac/dc or 24Vac/dc
Max. Absorbed current: 42mA (nominal 35mA)
Probe: NTC with double isolation for 230Vac or 110Vac
version.
Display and measurement units:
- 50.0 to 99.9 °C => 100 to110°C; -40 to 230 °F
NTC standard probe: -30 to 105°C (-22 to 220°F)
Display update delay times (optional) when the
temperature increases: fixed at 1 or 3 minutes
depending on model specified at time of order.
Operating temperature: 0 to 60°C/32 to 140°F
Storage temperature: -30 to 75°C/-22 to 167°F.
Relative humidity: 20 to 85% (non condensing)
Maximum working height: 2,000m a. s. l. (6,521 feet)
Installation category III; Transitory over-voltage: 4,000V
Pollution degree: 2 according to IEC 664.
Offset: ±10°C (±17°F)
Accuracy: from -30 to -10°C (-22 to 14°F): 1°C (2 °F) ±1
digit
from -10 to 110°C (14 to 230°F): 0.5°C (1 °F) ±1 digit
: