AKKU SYS 9885155 Podręcznik użytkownika - Strona 8

Przeglądaj online lub pobierz pdf Podręcznik użytkownika dla UPS AKKU SYS 9885155. AKKU SYS 9885155 12 stron. Extended battery pack 24v, 48v, 72v

AKKU SYS 9885155 Podręcznik użytkownika
User Manual
Extended Battery Pack 1kVA, 2kVA, 3kVA

4. Operation

Configuring Battery Settings
Set the UPS for the number of EBPs installed.
To ensure maximum battery runtime configure the UPS for the correct number of
EBPs refer to Figure 3 for the appropriate setting of battery numbers and type. Use the
up and down buttons to select the number of battery strings according to your UPS
configuration:
Figure 3 – Battery number configuration
All UPS and EBP Cabinets
UPS only (internal batteries)
USV + 1 Extended Battery Pack
USV + 2 Extended Battery Packs
USV + 3 Extended Battery Packs
USV + 4 Extended Battery Packs
NOTE:
The UPS contains one battery string; each EBP contains two battery strings.
Page 8
Number of Battery Strings
1 (default)
3
5
7
9
09/2021