CLEMAP Load Management Instrukcja instalacji - Strona 7
Przeglądaj online lub pobierz pdf Instrukcja instalacji dla Systemy kontroli CLEMAP Load Management. CLEMAP Load Management 13 stron.
CLEMAP Load Management | Installation manual
a. make sure that the power supply in the fuse box is disconnected.
b. position the CLEMAP product (a) so that the current sensors (b) can be easily connected to the
main input cables (L1, L2 and L3) (as shown in Fig. 2).
c. Attach the CLEMAP product to the fuse box.
d. Connect the current sensors (b) to the insulated incoming power lines (L1, L2 and L3),
making sure that the arrow shown in figure 3 points in the direction of the electrical loads .
e. connect the current sensors (b) to the CLEMAP product and make sure that the current sensors
of the L1, L2 and L3 cables match the corresponding voltage inputs L1, L2 and L3.
f. Connect the inputs N, L1, L2 and L3 to the corresponding voltage lines after fusing
(maximum 16 A).
g. Switch on the fuses and wait 3 minutes until the sensor is active.
POWER LED- feedback
OFF
The CLEMAP product is currentless.
ON
The CLEMAP product is switched on.
STATUS LED feedback
OFF
Hotspot Mode
The CLEMAP product has no connection to a LAN or WLAN network, so it creates its own
hotspot (see step 2 on the next page).
Slow
The WiFi login data is configured, an attempt is made to establish a connection to the
Flashing
WiFi.
Flashing The CLEMAP product is connected to a network.
It is currently seeking communication with the Internet.
ON
The CLEMAP product is connected to a WLAN network or connected via an Ethernet
cable and receives data from the Internet.
RESET button
pressed between 1
and 5 seconds
pressed between 5
and 10 seconds
pressed for more
than 10 seconds
Hotspot Mode
If the CLEMAP product does not have a connection to a LAN or WLAN
network, it will create its own hotspot (see step 2 on the next page).
Restart
The CLEMAP product is restarted.
Reset saved WIFI
The saved WIFI is deleted and the CLEMAP product creates a new hotspot.
7