Altronix AL1042UL2ADA Instrukcja instalacji - Strona 7
Przeglądaj online lub pobierz pdf Instrukcja instalacji dla Przedłużacz Altronix AL1042UL2ADA. Altronix AL1042UL2ADA 12 stron. Nac power extender
Fig. 2
Fig. 2A
Plastic
Washer
Power Supply
Board
Stand-Off
Ground Fault
Detection Disabled
(Factory Set)
unswitched 120VAC
60 Hz, 5 amp
power mains
(non power limited)
Green Lead
Fig. 2D
Optional hookups:
1- Battery and AC monitoring: AC or Battery Fail condition will cause the common trouble input [C "FAULT" NC]
to report back to the FACP via input 1 and input 2. The common trouble input may also be used for other optional
supervisory monitoring.
To report AC and Battery Trouble connect the battery and AC Fail relay output to the
common trouble input (Fig. 2).
2- Dry contact input [C "DRY1" NC] [C "DRY2" NC] can be used to alarm output from an addressable
module (these inputs are unidirection and cannot report back to trigger module).
Note: If common trouble input, terminals marked [C "FAULT" NC] are not used, these terminals must be shorted
(together) to remain inactive. For optional hookups, (Fig. 2).
3- Auxiliary outputs provide 24VDC at 1 amp max per output. The output voltage is determined by
the setting of switch marked SW1 on the Power Supply Board (Fig. 2).
"AUX1" will be automatically disabled during power failure. (use this for non required backup power)
"AUX2" will remain operational during allowable power failure. Refer to stand-by chart for stand-by
and alarm current.
Ground Fault Detect: Factory set disabled (Fig. 2A). To enable ground fault detection remove insulating washer
between the board and standoff of the lower right power supply board mounting screw (Fig. 2B).
AL1042UL2ADA
Optional Hookup Diagram:
Fig. 2B
Plastic
Washer
Ground Fault
Power Supply
Detection
Board
Enabled
Stand-Off
Fuse
Cover
These circuits are used to
monitor AC and Bat Fail and
will cause a simultaneous trouble
condition to the FACP's IN1 and IN2
(See Typical Application
Diagram for device hookup)
Addressable
control module
Power Limited Outputs
trigger output
2.5 amp per output max.
(total= 10 amp)
NC "DRY2" C
-- RET2 +
-- RET1 +
-- LOOP1 +
NC "DRY1" C
-- IN2 +
-- IN1 +
-- OUT1 +
Factory Installed
Board Interface
Cable
OUT1
OUT3
IN>OUT SYNC
STROBE SYNC
FAULT
INP2 INP1
TEMPORAL
INPUT SELECT
OUT2
OUT4
IN>OUT SYNC
OUT1 OUT2 OUT3 OUT4
STROBE SYNC
TEMPORAL
INPUT SELECT
Magnetic
Door Holder
4-wire Smoke
Detector
Fire
Alarm
Control
Panel
(FACP)
-- LOOP2 +
-- LOOP3 +
-- LOOP4 +
-- AUX2 +
AC
-- OUT2 +
-- OUT3 +
-- OUT4 +
-- AUX1 +
RESET
+ DC ---
4-wire Smoke
Detector
EOL Power
Supervision Relay
(Not Supplied)
EOL Resistor
from FACP
Fig. 2C
- 7 -